G7 ASD Operation Manual
181
Trip Monitor From ASD
The Trip Monitor From ASD function records the trip name of up to four trips and catalogs each trip as
Most Recent, Second Most Recent, Third Most Recent, and Fourth Most Recent. Once reset (Clear
Trip), the trip records are erased. If no trips have occurred since the last reset, No Fault is displayed for
each trip record.
Note:
An improper ASD setup may cause some trips — reset the ASD to the Factory Default
settings before pursuing a systemic malfunction (Program
⇒
Utility Parameters
⇒
Type Reset
⇒
Restore Factory Defaults).
Trip Record at Monitor Screen
The at-trip condition of the last incurred trip may be viewed at the Monitor screen (see
pg. 45
). The
Monitor screen at-trip record is erased when the ASD is reset and may be viewed without the use of the
RTC option.
Clearing a Trip
Once the cause of the trip has been corrected, performing a
Reset
re-enables the ASD for normal
operation.
The record of a trip may also be cleared using either of the following methods:
• Cycling power (trip info may be saved via
F602
if desired),
• Pressing the Stop|Reset key twice,
• Remotely via the communications channel,
• Momentarily connecting terminal RES to CC of the Control Terminal Strip, or
• Via Program
⇒
Utility Parameters
⇒
Type Reset
⇒
Clear Trip (clears Trip Monitor From ASD).