Direct Access Parameter Information
PTC 2 Thermal Selection
Program
Special
Special Parameters
This parameter Enables/Disables the optional external thermal
detection circuit of the Expansion IO Card Option 2. A thermistor
is connected from TH1+ to TH1- of TB4 on the Expansion IO
Card Option 2.
Should the thermistor resistance reading fall below 50W because
of an over-temperature condition or exceed 3000W because of
an open circuit, an External Thermal Fault (OH2) will be incurred.
Note: While this parameter is Enabled, the system cannot be
restarted until the thermistor value recovers to the level of
1.8 k
from an over-temperature condition. An Auto-
Restart will not be initiated subsequent to an External
Thermal Trip (OH2). A manual restart will be required in the
event of an OH2 trip.
Settings:
0 — Disabled
1 — Detect Disconnect
Direct Access Number —
F638
Parameter Type — S
election List
Factory Default —
Disabled
Changeable During Run —
No
Braking Resistance Overload Time (not used)
Program
Protection
Dynamic Braking
This parameter sets the time that the braking resistor is allowed
to sustain an overload condition before a trip is incurred.
This feature is useful for applications that have a fluctuating load
or for loads that require a long deceleration time.
Direct Access Number —
F639
Parameter Type —
Numerical
Factory Default —
5.0
Changeable During Run —
No
Minimum — 0.1
Maximum — 600.0
Units — Seconds
Step-Out Detection Current Level (for PM motors)
Program
Motor
PM Motor
This parameter is used with synchronous motor applications only.
Contact the TIC Customer Support Center for information on this
parameter.
Direct Access Number —
F640
Parameter Type —
Numerical
Factory Default —
100
Changeable During Run —
No
Minimum — 10
Maximum — 150
Units — %
Step-Out Detection Current Time (for PM motors)
Program
Motor
PM Motor
This parameter is used with synchronous motor applications only.
Contact the TIC Customer Support Center for information on this
parameter.
Direct Access Number —
F641
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
No
Minimum — 0.0
Maximum — 25.0
Units — Seconds
Содержание DN-68249-003
Страница 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Страница 2: ......
Страница 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Страница 305: ......