Direct Access Parameter Information
End Frequency
Program
Special
Frequency Control
This parameter sets the lowest frequency that the ASD will recog
-
nize during deceleration before the ASD goes to 0.0 Hz.
Direct Access Number —
F243
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — (ASD-Dependent)
Units — Hz
0 Hz Dead Band Signal
Program
Special
Special Parameters
This parameter sets an output frequency threshold that, until the
commanded frequency surpasses this setting, the ASD will out
-
put 0.0 Hz to the motor.
This setting will override the Start Frequency setting (
) if this
setting has a higher value.
Direct Access Number —
F244
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — (ASD-Dependent)
Units — Hz
DC Injection Braking Start Frequency
Program
Protection
DC Braking
During deceleration, this is the frequency at which DC Injection
Braking will start.
DC Injection Braking
DC Injection Braking is a braking system used with 3-phase
motors. Unlike conventional brakes, there is no physical contact
between the rotating shaft and a stationary brake pad or drum.
When braking is required, the ASD outputs a DC current that is
applied to the windings of the motor to quickly brake the motor.
The braking current stops when the time entered in
times
out.
The intensity of the DC current used while braking determines
how fast the motor will come to a stop and may be set at
.
The intensity setting is entered as a percentage of the full load
current of the ASD.
DC Injection Braking is also used to preheat the motor or to keep
the rotor from spinning freely when the motor is off by providing a
pulsating DC current into the motor at the Carrier Frequency. This
feature may be enabled at
Direct Access Number —
F250
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — (ASD-Dependent)
Units — Hz
DC Injection Braking Current
Program
Protection
DC Braking
This parameter sets the percentage of the rated current of the
ASD that will be used for DC Injection Braking. A larger load will
require a higher setting.
Direct Access Number —
F251
Parameter Type —
Numerical
Factory Default —
50
Changeable During Run —
Yes
Minimum — 0
Maximum — 100
Units — %
Содержание DN-68249-003
Страница 1: ...ADJUSTABLE SPEED DRIVES Q9 DN 68249 003 INSTALLATION OPERATION MANUAL April 2020 ...
Страница 2: ......
Страница 3: ...Document Number 68249 003 April 2020 Q9 Plus ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...Table of Contents Q9 Plus ASD Install Op Manual iv https www toshiba com tic ...
Страница 305: ......