(2) STANDARD OPERATION CIRCUIT
Shown below are the vacuum contactor and its auxiliary circuits (control and
monitoring).
Fig.6 represents the standard operation circuit of the normally energized type
and Fig.7 the latched type.
Wiring should be done according to these circuit diagrams.
Du
5
1
6
2
T1
T5 T6 T7
T10
T11
T15 T16 T17
T19
T18
10
11
12
8
9
7
6
5
4
3
1
AUS
2
52CC
T8
T9
T20
OFF
REMOTE
SWITCH
ON
START
INTERLOCK
STOP
INTERLOCK
2E-RY
4
E
E
E
E
4
4
VMC
AC
100
-24
0V
DC
100
-22
0V
COS
*1
Fig.6 Standard operation circuit of normally energized type.
NOTE:
●
Be sure to use quickly AC auxiliary relay contact NO for self
-
holding.
If the self
-
holding circuit is formed by using the auxiliary contact No
of the vacuum contactor , welding of the main contact may result when
the start button is pushed incompletely(refer to *1 in Fig.6).