The drive unit for the electromagnet is installed in the bottom frame.
Molded and wired on the printed circuit.
The closing circuit can be operated using either in AC or DC by the drive unit.
The optional latch trip circuit uses DC as standard.
When a latched contactor is operated using AC power, it is recommended that a
Capacitor trip device be used.
The standard operating voltage is as follows:
Non-latched type(normally energized) : 100
-
240 V AC /100
-
220V DC
Latched type :100
-
240V AC /100
-
250V DC closing voltage
:100
-
110V DC tripping voltage
1
2
SWITCHING
OSCILLATION
POWER
TIMER
VOLTAGE
DETECT
52CC
Diode
(Latched type)
Fig.3 Internal Configuration of Drive Unit
CAUTION : Do not touch the drive unit without trouble.