– 10 –
EN
<Under air intake>
Alteration from the back air intake to the underside air intake
Remove the cover plate from underside. Attach the cover plate to back air intake side.
The intake flange provided (for air intake from the back) cannot be used for air intake from the underside.
31.7”(805)
3.9”(100) 3.9”(100) 3.9”(100) 3.9”(100) 3.9”(100) 3.9”(100) 3.9”(100) 3.9”(100)
0.5”(12.5)
0.5”(12.5)
1.
8”
(4
5
.3)
3.
9”
(1
00
)
3.9”
(100
)
1.
6”
(41.
5)
0.
3”
(8
.2
) or
le
ss
11.
3”
(286
.8
)
10
.5
”(
26
6)
32.5”(825)
Remove the cover plate and then fix
it to the air intake side
Take out this cover
plate.
CAUTION
Connecting method of the duct
CAUTION
Incomplete heat insulation of the supply air flange and sealing may occur dewing resulted in falling of water drop.
Flange
Aluminum tape (locally procured)
Aluminum tape (locally procured)
Under surface
Cover a screw
Heat insulator with sticking material (locally procured)
Aluminum tape
(locally procured)
Air discharge side
Indoor unit
Air intake side
Connect a duct to the
inside of the flange
Heat insulator with sticking material (locally procured)
Aluminum tape (locally procured)
Duct: Insulation
materia
(locally procured)
Flange
19-EN
20-EN