Timer setting
(wired remote controller)
0000: Available (can be performed)
0001: Unavailable (cannot be performed)
0000: Available
DN
Item
Description
At shipment
Type
DN code “10”
*1 Default value stored in EEPROM mounted on service P.C. board
Indoor Unit Capacity
DN code “11”
*1 Default value stored in EEPROM
mounted on service P.C. board
Value
Type
Model
0004
Medium static ducted type
ޓ
MMD-AP
BH2UL
Value
Capacity
0000*
Invalid
0001
007 type
0003
009 type
0005
012 type
0007
015 type
0009
018 type
0011
024 type
0010
021 type
0012
027 type
0013
030 type
0015
036 type
0017
048 type
0016
042 type
0018
056 type
0021
072 type
0023
096 type
~
–
92
Outside interlock
release condition
0000: Operation stop
0001: Release communication signal receive
0000: Operation stop
DIP Switch
position
SET DATA
External static
pressure
0000
0001
0003
0006
0.008psi (55Pa)
0.013psi (90Pa)
0.017psi (120Pa)
0.006psi (40Pa)
(Factory default)
High static pressure 1
High static pressure 3
Low static pressure
Standard
***
SW01
SW02
SW01
SW02
SW01
SW02
SW01
SW02
OFF OFF OFF OFF
OFF ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF OFF
OFF OFF OFF ON
OFF ON OFF ON
1 2
1 2
1 2
1 2
1 2
1 2
1 2
1 2