Check codes and parts to be checked

Check method

On the remote control (Wired remote control, Central control remote control) and the interface P.C. board of the 
outdoor unit (I/F), a check display LCD (Remote control) or 7-segment display (on the outdoor interface P.C. board) 
to display the operation is provided. Therefore the operation status can be known. With this self-diagnosis function, 
a trouble or position with error of the air conditioner can be found as shown in the table below.

Check code list

The following list shows each check code. Find the check contents from the list according to part to be checked.
• To check from indoor remote control: See “Wired remote control display” in the list.
• To check from outdoor unit: See “Outdoor 7-segment display” in the list.
• To check from indoor unit with a wireless remote control: See “Sensor block display of receiving unit” in the list.

IPDU : Intelligent Power Drive Unit

: Lighting, 

: Flashing, 

: Goes off

ALT. : Flashing is alternately when there are two flashing LED.
SIM : Simultaneous flashing when there are two flashing LED.

Check code

Wireless remote control

Check code name

Judging device

Wired remote 

control display

Outdoor 7-segment display

Sensor block display of 

receiving unit

Auxiliary code

Operation Timer Ready Flash

E01

Communication error between indoor and remote 

control 

(Detected at remote control side)

Remote control

E02

Remote control transmission error

Remote control

E03

Communication error between indoor and remote 

control (Detected at indoor side)

Indoor

E04

Communication circuit error between indoor/

outdoor (Detected at indoor side)

Indoor

E06

E06

No. of indoor units in which 

sensor has been normally 

received

Decrease of No. of indoor units

I/F

E07

Communication circuit error between indoor/

outdoor (Detected at outdoor side)

I/F

E08

E08 Duplicated indoor addresses

Duplicated indoor addresses

Indoor / I/F

E09

Duplicated header remote controls

Remote control

E10

Communication error between indoor MCU

Indoor

E12

E12

01: Indoor/Outdoor 

communication

02: Communication between 

outdoor units

Automatic address start error

I/F

E15

E15

Indoor is nothing during automatic addressing

I/F

E16

E16 00: Capacity over

01 ~:No. of connected units

Capacity over / No. of connected indoor units

I/F

E18

Communication error between indoor units

Indoor

E19

E19 00: Header is nothing

02: Two or more header units

Outdoor header units quantity error

I/F

E20

E20

01: Outdoor of other line 

connected

02: Indoor of other line connected

Other line connected during automatic

address

I/F

E23

E23

Sending error in communication between

outdoor units

I/F

E25

E25

Duplicated follower outdoor addresses

I/F

E26

E26 No. of outdoor units which 

received signal normally

Decrease of No. of connected outdoor units

I/F

E28

E28 Detected outdoor unit number

Follower outdoor unit error

I/F

E31

E31

IPDU communication error

I/F

F01

ALT Indoor TCJ sensor error

Indoor

F02

ALT Indoor TC2 sensor error

Indoor

F03

ALT Indoor TC1 sensor error

Indoor

F04

F04

ALT TD1 sensor error

I/F

F05

F05

ALT TD2 sensor error

I/F

F06

F06 TE1 sensor

TE2 sensor

ALT TE1 sensor error

TE2 sensor error

I/F

F07

F07

ALT TL sensor error

I/F

F08

F08

ALT TO sensor error

I/F

F10

ALT Indoor TA sensor error

Indoor

F12

F12

ALT TS1 sensor error

I/F

F13

F13

01: Comp. 1 side

02: Comp. 2 side

03: Comp. 3 side 

ALT TH sensor error

IPDU

F15

F15

ALT Outdoor temp. sensor miswiring (TE1, TL)

I/F

F16

F16

ALT Outdoor pressure sensor miswiring (Pd, Ps)

I/F

F22

F22

ALT TD3 error

I/F

F23

F23

ALT Ps sensor error

I/F

F24

F24

ALT Pd sensor error

I/F

F29

SIM Indoor other error

Indoor

F31

F31

SIM Indoor EEPROM error

I/F

H01

H01

01: Comp. 1 side

02: Comp. 2 side

03: Comp. 3 side

Compressor break down

IPDU

H02

H02

01: Comp. 1 side

02: Comp. 2 side

03: Comp. 3 side

Compressor trouble (lock)

IPDU

H03

H03

01: Comp. 1 side

02: Comp. 2 side

03: Comp. 3 side

Current detect circuit system error

IPDU

H05

H05

TD1 miswiring

I/F

H06

H06

Low pressure protective operation

I/F

H07

H07

Oil level down detective protection

I/F

H08

H08

01: TK1 sensor error

02: TK2 sensor error

03: TK3 sensor error

04: TK4 sensor error

Oil level detective temp sensor error

I/F

H15

H15

TD2 miswiring

I/F

Check code

Wireless remote control

Check code name

Judging device

Wired remote 

control display

Outdoor 7-segment display

Sensor block display of 

receiving unit

Auxiliary code

Operation Timer Ready Flash

A3-IPDU

Fan 

IPDU

1

2

3

01

c

02

c

03

c

c

04

c

05

c

c

06

c

c

07

c

c

c

08

c

09

c

c

0A

c

c

0B

c

c

c

0C

c

c

0D

c

c

c

0E

c

c

c

0F

c

c

c

c

c

 : IPDU error

27-EN

28-EN

+00EH99876401_00Ta.book  Page 14  Monday, January 17, 2011  10:47 AM

Содержание Carrier MMC-AP0181H2UL

Страница 1: ...uel d installation 17 Français AIR CONDITIONER MULTI TYPE Indoor Unit Model name Ceiling type MMC AP0181H2UL MMC AP0241H2UL MMC AP0361H2UL MMC AP0421H2UL Installation manual 00EH99876401_00Ta book Page 1 Monday January 17 2011 10 47 AM ...

Страница 2: ...ly refrigerant 1 Accessory Parts Accessory parts Part name Q ty Shape Usage Installation Manual 1 This manual Installation pattern 1 Drawing out port of hanging bolt pipe Heat insulation pipe 2 For heat insulation of pipe connecting section Washer 4 3 8 M10 Ø1 0 25 mm For holding down unit Hose band 2 For connecting drain pipe Drain hose 1 For connecting drain pipe Bushing Ø2 2 Ø56 1 For protectio...

Страница 3: ... cycle If air or any other gas is mixed in the refrigerant the gas pressure in the refrigeration cycle becomes abnormally high and it resultingly causes pipe burst and injuries on persons Perform installation work properly according to the Installation Manual Inappropriate installation may result in water leakage electric shock or fire When the air conditioner is installed in a small room provide ...

Страница 4: ... abnormal control or problems due to noise to such appliances equipment may occur When the wireless remote control is used in a room equipped with an inverter type fluorescent light or at a place exposed to direct sunlight signals from the remote control may not be received correctly Place where organic solvent is used Place near a door or window exposed to humid outside air Dew drop may form Plac...

Страница 5: ... only Do not apply force to the other parts refrigerant pipe drain pan foamed parts or resin parts Carry the package by two or more persons and do not bundle it with plastic band at positions other than specified External view Unit in mm A Unit in mm Model MMC A B C D AP018 35 8 910 33 7 855 Ø1 4 6 4 Ø1 2 12 7 AP024 46 5 1180 44 3 1125 Ø3 8 9 5 Ø5 8 15 9 AP036 AP042 62 8 1595 60 6 1540 Conduit hol...

Страница 6: ...nchor bolts Steel flame structure Use existing angles or install new support angles Existing concrete slab Use a hole in anchors hole in plugs or a hole in bolts Ceiling surface Installation pattern Wall face Rubber Anchor bolt Blade type bracket Slide type bracket Pipe hanging anchor bolt Hanging bolt Hanging bolt Support angle 100 Rear cover Opened when refrigerant pipe is taken out from the rea...

Страница 7: ...ction CAUTION Do not apply excessive torque Otherwise the nut may crack depending on the conditions Tightening torque of flare pipe connections Pressure of R410A is higher than that of R22 Approx 1 6 times Use a torque wrench tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque Incorrect connections may cause not only a gas leak b...

Страница 8: ...2 m Arched shape Trap NO GOOD VP25 As long as possible 3 9 100 mm Downward slope 1 100 or more VP30 or more VP25 VP25 Drain pipe connecting port Hard socket Attached flexible hose VP20 vinyl chloride pipe procured locally Soft socket Soft socket Adhesive agent prohibited Attached hose band Attached hose band Drain pan Plug Drain pan Drain up When not securing down slope on the drain pipe use a Dra...

Страница 9: ...y be caused Indoor unit power supply For the power supply of the indoor unit prepare the exclusive power supply separated from that of the outdoor unit Power supply Control wiring Central control wiring 2 core with non polarity wires are used for the control wiring between indoor unit and outdoor unit and Central control wiring To prevent noise trouble use 2 core shielded wire The length of the co...

Страница 10: ...the control wire and the remote control wire Do not connect the high voltage circuit Loosen the cover mounting screws 2 positions of the electrical control box and then remove the cover Attach the conduit pipe to the conduit hole with a lock nut Slit the film of bushing attached to the hole for control wire and remote control wire and then pass through wires Connect the power supply wires control ...

Страница 11: ...minal numbers on the indoor units and circuit breakers terminal blocks and firmly screw the wires to the corresponding terminals 3 Secure the ground wire with the ground screw 4 Fix the wires with a cord clamp Unit in mm CAUTION Firmly tighten the screws of the terminal block Keep the wire length as shown in figure below when it is connected to the terminal block Control wires Because a hole for c...

Страница 12: ... 6 1 3 2 5 4 Display content varies with the indoor unit model Procedure 3 Specify CODE No with temp setup buttons Procedure 4 Select SET DATA with timer time buttons Procedure 5 Push button When the display changes from flashing to lit the setup is completed To change settings of another indoor unit repeat from Procedure 2 To change other settings of the selected indoor unit repeat from Procedure...

Страница 13: ...For address setup refer to the Installation Manual attached to the outdoor unit SET DATA Filter sign lighting time 0000 None 0001 150 H 0002 2500 H Factory default 0003 5000 H 0004 10000 H SET DATA Detection temp shift value 0000 No shift 0001 1 8 F 1 C 0002 3 6 F 2 C Factory default 0003 5 4 F 3 C 0004 7 2 F 4 C 0005 9 0 F 5 C 0006 10 8 F 6 C SET DATA 0000 0001 Remote control sensor Not used fact...

Страница 14: ...ttons Cooling test run Heating test run After confirming a signal receiving sound beep immediately set the temperature to 64 F 18 C with the temp setup buttons After confirming a signal receiving sound beep immediately set the temperature to 86 F 30 C with the temp setup buttons 3 4 5 6 2 7 2 2 Always select HIGH fan speed 10Troubleshooting Confirmation and check When an error occurred in the air ...

Страница 15: ...F E16 E16 00 Capacity over 01 No of connected units Capacity over No of connected indoor units I F E18 Communication error between indoor units Indoor E19 E19 00 Header is nothing 02 Two or more header units Outdoor header units quantity error I F E20 E20 01 Outdoor of other line connected 02 Indoor of other line connected Other line connected during automatic address I F E23 E23 Sending error in ...

Страница 16: ...d remote control display Outdoor 7 segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash A3 IPDU Fan IPDU 1 2 3 01 c 02 c 03 c c 04 c 05 c c 06 c c 07 c c c 08 c 09 c c 0A c c 0B c c c 0C c c 0D c c c 0E c c c 0F c c c c c IPDU error Error detected by TCC LINK central control device TCC LINK TOSHIBA Carrier Communication Link P18 P18 ALT Discharge temp T...

Страница 17: ...E 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 22lbs 10kg The possible amount of leaked refrigerant gas in rooms D E and F is 33lbs 15kg NOTE 2 The standards for minimum room volume...

Страница 18: ...CEILING 1 0001 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively For check method refer to Applicable controls in this manual Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 ...

Отзывы: