Installation manual

1

English

Manuel d’installation

17

Français

AIR CONDITIONER (MULTI TYPE)

Indoor Unit

Model name:

Ceiling type

MMC-AP0181H2UL
MMC-AP0241H2UL
MMC-AP0361H2UL
MMC-AP0421H2UL

Installation manual

+00EH99876401_00Ta.book  Page 1  Monday, January 17, 2011  10:47 AM

Содержание Carrier MMC-AP0181H2UL

Страница 1: ...uel d installation 17 Français AIR CONDITIONER MULTI TYPE Indoor Unit Model name Ceiling type MMC AP0181H2UL MMC AP0241H2UL MMC AP0361H2UL MMC AP0421H2UL Installation manual 00EH99876401_00Ta book Page 1 Monday January 17 2011 10 47 AM ...

Страница 2: ...ly refrigerant 1 Accessory Parts Accessory parts Part name Q ty Shape Usage Installation Manual 1 This manual Installation pattern 1 Drawing out port of hanging bolt pipe Heat insulation pipe 2 For heat insulation of pipe connecting section Washer 4 3 8 M10 Ø1 0 25 mm For holding down unit Hose band 2 For connecting drain pipe Drain hose 1 For connecting drain pipe Bushing Ø2 2 Ø56 1 For protectio...

Страница 3: ... cycle If air or any other gas is mixed in the refrigerant the gas pressure in the refrigeration cycle becomes abnormally high and it resultingly causes pipe burst and injuries on persons Perform installation work properly according to the Installation Manual Inappropriate installation may result in water leakage electric shock or fire When the air conditioner is installed in a small room provide ...

Страница 4: ... abnormal control or problems due to noise to such appliances equipment may occur When the wireless remote control is used in a room equipped with an inverter type fluorescent light or at a place exposed to direct sunlight signals from the remote control may not be received correctly Place where organic solvent is used Place near a door or window exposed to humid outside air Dew drop may form Plac...

Страница 5: ... only Do not apply force to the other parts refrigerant pipe drain pan foamed parts or resin parts Carry the package by two or more persons and do not bundle it with plastic band at positions other than specified External view Unit in mm A Unit in mm Model MMC A B C D AP018 35 8 910 33 7 855 Ø1 4 6 4 Ø1 2 12 7 AP024 46 5 1180 44 3 1125 Ø3 8 9 5 Ø5 8 15 9 AP036 AP042 62 8 1595 60 6 1540 Conduit hol...

Страница 6: ...nchor bolts Steel flame structure Use existing angles or install new support angles Existing concrete slab Use a hole in anchors hole in plugs or a hole in bolts Ceiling surface Installation pattern Wall face Rubber Anchor bolt Blade type bracket Slide type bracket Pipe hanging anchor bolt Hanging bolt Hanging bolt Support angle 100 Rear cover Opened when refrigerant pipe is taken out from the rea...

Страница 7: ...ction CAUTION Do not apply excessive torque Otherwise the nut may crack depending on the conditions Tightening torque of flare pipe connections Pressure of R410A is higher than that of R22 Approx 1 6 times Use a torque wrench tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque Incorrect connections may cause not only a gas leak b...

Страница 8: ...2 m Arched shape Trap NO GOOD VP25 As long as possible 3 9 100 mm Downward slope 1 100 or more VP30 or more VP25 VP25 Drain pipe connecting port Hard socket Attached flexible hose VP20 vinyl chloride pipe procured locally Soft socket Soft socket Adhesive agent prohibited Attached hose band Attached hose band Drain pan Plug Drain pan Drain up When not securing down slope on the drain pipe use a Dra...

Страница 9: ...y be caused Indoor unit power supply For the power supply of the indoor unit prepare the exclusive power supply separated from that of the outdoor unit Power supply Control wiring Central control wiring 2 core with non polarity wires are used for the control wiring between indoor unit and outdoor unit and Central control wiring To prevent noise trouble use 2 core shielded wire The length of the co...

Страница 10: ...the control wire and the remote control wire Do not connect the high voltage circuit Loosen the cover mounting screws 2 positions of the electrical control box and then remove the cover Attach the conduit pipe to the conduit hole with a lock nut Slit the film of bushing attached to the hole for control wire and remote control wire and then pass through wires Connect the power supply wires control ...

Страница 11: ...minal numbers on the indoor units and circuit breakers terminal blocks and firmly screw the wires to the corresponding terminals 3 Secure the ground wire with the ground screw 4 Fix the wires with a cord clamp Unit in mm CAUTION Firmly tighten the screws of the terminal block Keep the wire length as shown in figure below when it is connected to the terminal block Control wires Because a hole for c...

Страница 12: ... 6 1 3 2 5 4 Display content varies with the indoor unit model Procedure 3 Specify CODE No with temp setup buttons Procedure 4 Select SET DATA with timer time buttons Procedure 5 Push button When the display changes from flashing to lit the setup is completed To change settings of another indoor unit repeat from Procedure 2 To change other settings of the selected indoor unit repeat from Procedure...

Страница 13: ...For address setup refer to the Installation Manual attached to the outdoor unit SET DATA Filter sign lighting time 0000 None 0001 150 H 0002 2500 H Factory default 0003 5000 H 0004 10000 H SET DATA Detection temp shift value 0000 No shift 0001 1 8 F 1 C 0002 3 6 F 2 C Factory default 0003 5 4 F 3 C 0004 7 2 F 4 C 0005 9 0 F 5 C 0006 10 8 F 6 C SET DATA 0000 0001 Remote control sensor Not used fact...

Страница 14: ...ttons Cooling test run Heating test run After confirming a signal receiving sound beep immediately set the temperature to 64 F 18 C with the temp setup buttons After confirming a signal receiving sound beep immediately set the temperature to 86 F 30 C with the temp setup buttons 3 4 5 6 2 7 2 2 Always select HIGH fan speed 10Troubleshooting Confirmation and check When an error occurred in the air ...

Страница 15: ...F E16 E16 00 Capacity over 01 No of connected units Capacity over No of connected indoor units I F E18 Communication error between indoor units Indoor E19 E19 00 Header is nothing 02 Two or more header units Outdoor header units quantity error I F E20 E20 01 Outdoor of other line connected 02 Indoor of other line connected Other line connected during automatic address I F E23 E23 Sending error in ...

Страница 16: ...d remote control display Outdoor 7 segment display Sensor block display of receiving unit Auxiliary code Operation Timer Ready Flash A3 IPDU Fan IPDU 1 2 3 01 c 02 c 03 c c 04 c 05 c c 06 c c 07 c c c 08 c 09 c c 0A c c 0B c c c 0C c c 0D c c c 0E c c c 0F c c c c c IPDU error Error detected by TCC LINK central control device TCC LINK TOSHIBA Carrier Communication Link P18 P18 ALT Discharge temp T...

Страница 17: ...E 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 22lbs 10kg The possible amount of leaked refrigerant gas in rooms D E and F is 33lbs 15kg NOTE 2 The standards for minimum room volume...

Страница 18: ...CEILING 1 0001 Have you changed lighting time of filter sign If not fill check mark in NO CHANGE and fill check mark in ITEM if changed respectively For check method refer to Applicable controls in this manual Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 10000H 0004 Filter sign lighting time CODE No 01 NO CHANGE NONE 0000 150H 0001 2500H 0002 5000H 0003 ...