8-2. Energy Monitoring Relay Interface (BMS-IFWH5E)
The following settings are necessary to use Energy Monitoring Relay Interfaces.
Address setting
SW1 Address set switch
When two or more Energy Monitoring Relay Interfaces are used, set a different address for each unit
to avoid address duplication.
RS-485 terminator resistor
setting
Set SW7 as “120 ohm” on a Energy Monitoring Relay Interface with address SW1=1, and “Open” on
the other interfaces.
SW1
Address set switch
1-8
Address
0, 9-F
Not used
SW2
Operating mode set switch (0 usually)
SW3
Test switch (all OFF usually)
SW4
Test switch
SW6
Reset switch
SW7
RS-485 terminator resistor select switch
120 ohm
Open
LED1
Power indicator
LED2
RS-485 communication status indicator
LED3
Not used
LED4
Test indicator
LED5
Test indicator
ON
ON
L
N
BA
S
G
RS-485
DI
1
DI
6
DI
2
DI
4
DI
3
DI
7
DI
8
DI
5
1 2 3 4
LED1
LED2
LED3
LED4
LED5
SW1
SW2
SW3
SW4
SW6
SW7
+ -+
-+
-+
-
+ -
+ -+
-+
-