BN interface
Installation Manual
8
-EN
2
Power and signal line connections
Cables
Use the following cable for signal line connections. (Procured locally)
Ethernet
®
is a registered trademark of Xerox Co., Ltd.
Cable Connections
Connect the cables to the specified connectors.
Length of stripped TCC-LINK communication cable
CAUTION
The TCC-LINK communication cable have no polarity.
* Secure the TCC-LINK communication cable and power cable to the switchboard etc. using the supplied cable tie to
ensure that no excess load is placed on the power cable connection and TCC-LINK communication cable connection.
No.
Line
Description
1
For TCC-LINK
Type
2-core shielded wires
Wire size
1.25 mm
2
, 1000 m max.
total length
including air conditioner wiring length
Length
2.00 mm
2
, 2000 m max.
2
For Ethernet
®
Type
LAN cable (higher than Category 5, UTP)
The appropriate use of straight cable/cross cable should be done depending on your
system used
Length
100 m max.
50
10
Connect the supplied pin terminal to the TCC-LINK
communication cable as necessary.
7&&/,1.
9'&,1
(WKHUQHW/$1
Connection of TCC-
LINK Communication
Cables
Connect the
supplied power
adapter
Connect the LAN
cable
The TCC-LINK communication cable must
be earthed on the air conditioner.
Do not connect the shield wire to the
connector. It should be open and
insulated.
Air conditioner