H7 ASD Operation Manual
the oldest recorded trip will be deleted with each new record stored (first-in first-out). The Trip # field
may be selected and scrolled through to view the recorded trip information for a given trip number. The
monitored at-trip parameters are listed in
as At-trip Recorded Parameters.
Trip records zero and one are comprised of the full list of monitored parameters listed in
Table 8
. Trip
records 2 – 18 are comprised of the first 16 parameters of
and trip records 19 – 100 are comprised
of the first 7 parameters of
.
Table 8. Trip History Record Parameters (RTC option required).
Trip Monitor From ASD
The Trip Monitor From ASD function records the trip name of up to four trips and catalogs each trip as
Most Recent, Second Most Recent, Third Most Recent, and Fourth Most Recent. Once reset (Clear
Trip), the trip records are erased. If no trips have occurred since the last reset, No Fault is displayed for
each trip record.
Note:
An improper ASD setup may cause some trips — reset the ASD to the Factory Default
settings before pursuing a systemic malfunction (Program
⇒ Utility Parameters ⇒
Type Reset
⇒
Restore Factory Defaults)
.
Trip Record at Monitor Screen
The at-trip condition of the last incurred trip may be viewed at the Monitor screen. The Monitor screen
at-trip record is erased when the ASD is reset.
Clearing a Trip
Once the cause of the trip has been corrected, performing a
Reset
re-enables the ASD for normal
operation.
The record of a trip may also be cleared using either of the following methods:
•
Cycling power (trip info may be saved via
F602
if required),
•
Pressing the Stop|Reset key twice,
•
Remotely via the communications channel,
•
Momentarily connecting terminal RES to CC of the Control Terminal Strip, or
•
Via Program
⇒ Utility Parameters ⇒ Type Reset ⇒ Clear Trip (clears Trip Monitor From ASD).
At-trip Recorded Parameters
1) Trip Number
9) Bus Voltage
17) Torque Reference
25) ASD Load
2) Trip Type
10) Discrete Input Status
18) Torque Current
26) DBR Load
3) Time and Date
11) OUT1/OUT2/FL Status
19) Excitation Current
27) Input Power
4) Frequency at Trip
12) Timer
20) PID Value
28) Output Power
5) Output Current
13) Post Compensation Frequency
21) Motor Overload
29) Peak Current
6) Output Voltage
14) Feedback (inst.)
22) ASD Overload
30) Peak Voltage
7) Direction
15) Feedback (1 sec.)
23) DBR Overload
31) PG Speed
8) Frequency Reference
16) Torque
24) Motor Load
32) PG Position
www
. ElectricalPartManuals
. com
Содержание Adjustable Speed Drive H7 Series
Страница 198: ...H7 ASD Operation Manual Appendix A 191 Figure 23 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 199: ...192 Appendix A H7 ASD Operation Manual Figure 24 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 201: ...194 Appendix A H7 ASD Operation Manual Figure 26 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...