H7 ASD Operation Manual
169
RS485 Communications Time-Out Action
Program
⇒
Communication Setting Parameters
⇒
Communication
Settings
This parameter plays a role in the setup of the communications network by
determining the action to be taken in the event of a time-out (Time-Out
Action).
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the drive.
Settings:
No Action
Alarm
Trip
Direct Access Number — F804
Parameter Type — Selection List
Factory Default — Trip
Changeable During Run — Yes
Communication Interval
Program
⇒
Communication Setting Parameters
⇒
Communication
Settings
This parameter sets the Common Serial response delay time.
Direct Access Number — F805
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 2.00
Units — Seconds
TTL Master Output
Program
⇒
Communication Setting Parameters
⇒
Communication
Settings
In a master/follower configuration, this setting determines the output parameter
of the master ASD that will be used to control the applicable follower ASDs.
is configured as a Master Output controller.
Otherwise, an EOI failure will result.
Settings:
No Slave (normal operation)
Frequency Reference
Output Command Frequency
Torque Command
Output Torque Command
Direct Access Number — F806
Parameter Type — Selection List
Factory Default — No Slave (normal
operation)
Changeable During Run — Yes
www
. ElectricalPartManuals
. com
Содержание Adjustable Speed Drive H7 Series
Страница 198: ...H7 ASD Operation Manual Appendix A 191 Figure 23 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 199: ...192 Appendix A H7 ASD Operation Manual Figure 24 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 201: ...194 Appendix A H7 ASD Operation Manual Figure 26 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...