H7 ASD Operation Manual
117
Integral (I) Gain
Program
⇒
Feedback Parameters
⇒
Feedback Settings
This parameter provides a value that either increases or decreases the degree
that the Integral function affects the output signal. The smaller the value here,
the more pronounced the effect of the integral function on the output signal.
Direct Access Number — F363
Parameter Type — Numerical
Factory Default — 0.10
Changeable During Run — Yes
Minimum — 0.01
Maximum — 100.0
Feedback Settings Upper Deviation Limits
Program
⇒
Feedback Parameters
⇒
Feedback Settings
This parameter determines the maximum amount that the feedback may
increase the output signal.
Direct Access Number — F364
Parameter Type — Numerical
Factory Default — 50.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 50.00
Units — %
Feedback Settings Lower Deviation Limits
Program
⇒
Feedback Parameters
⇒
Feedback Settings
This parameter determines the maximum amount that the feedback may
decrease the output signal.
Direct Access Number — F365
Parameter Type — Numerical
Factory Default — 50.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 50.00
Units — %
Feedback Settings Differential (D) Gain
Program
⇒
Feedback Parameters
⇒
Feedback Settings
This parameter determines the degree that the differential function affects the
output signal. The larger the value entered here, the more pronounced the affect
of the differential function for a given feedback signal level.
Direct Access Number — F366
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.0
Maximum — 2.55
Number of PG Input Pulses
Program
⇒
Feedback Parameters
⇒
PG Settings
This parameter is used to set the end-of-travel range when using an encoder on
a motor-driven positioning system (e.g., hoist/crane, etc.).
Direct Access Number — F367
Parameter Type — Numerical
Factory Default — 500
Changeable During Run — No
Minimum — 1
Maximum — 9999
Units — Pulse Count
www
. ElectricalPartManuals
. com
Содержание Adjustable Speed Drive H7 Series
Страница 198: ...H7 ASD Operation Manual Appendix A 191 Figure 23 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 199: ...192 Appendix A H7 ASD Operation Manual Figure 24 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...
Страница 201: ...194 Appendix A H7 ASD Operation Manual Figure 26 w w w E l e c t r i c a l P a r t M a n u a l s c o m ...