Service Manual
, 2017-8
39
/
51
operation, fan motor or electric control panel can be replaced.
10.5
Refrigerator fan motor circuit(None)
10.6
Condensing fan motor circuit(None)
10.7
Damper motor circuit
The air damper is driven by stepping motor of 2 phase Take 4.it has 4
wires(white,blue,yellow ,red),driven voltage is 12V, the current is very low, max is 100mA, Take 4
is one cycle, if positive rotation, it controls according to above photo(step 1-4), if reverse rotation,
it controls according to step 4-1
10.8
Resistance value of the sensor (R/T)
Tx(
℃
)
R
(
KΩ
)
Tx(
℃
)
R
(
KΩ
)
Tx(
℃
)
R
(
KΩ
)
Tx(
℃
)
R
(
KΩ
)
Tx(
℃
)
R
(
KΩ
)
-30
33.81
-15
14.31
0
6.495
15
3.141
30
1.617
-29
31.85
-14
13.55
1
6.175
16
2.999
31
1.55
-28
30.01
-13
12.83
2
5.873
17
2.865
32
1.486
-27
28.29
-12
12.16
3
5.587
18
2.737
33
1.426
-26
26.68
-11
11.52
4
5.315
19
2.616
34
1.368
-25
25.17
-10
10.92
5
5.06
20
2.501
35
1.312
-24
23.76
-9
10.35
6
4.818
21
2.391
36
1.259
Содержание 22031020002961
Страница 5: ...Service Manual 2017 8 5 51 1 Safety Warning Code 1 1Warning for operation safety ...
Страница 6: ...Service Manual 2017 8 6 51 ...
Страница 7: ...Service Manual 2017 8 7 51 ...
Страница 8: ...Service Manual 2017 8 8 51 1 2Safety instruction for refrigerant ...
Страница 17: ...Service Manual 2017 8 17 51 5 5Circuit diagram ...
Страница 41: ...Service Manual 2017 8 41 51 ...
Страница 42: ...Service Manual 2017 8 42 51 11 2 Compressor failure ...
Страница 43: ...Service Manual 2017 8 43 51 11 3 Defrosting is not working ...
Страница 44: ...Service Manual 2017 8 44 51 ...
Страница 46: ...Service Manual 2017 8 46 51 11 5 Damper is abnormal 11 6 Lights inside the refrigerator don t light up ...
Страница 51: ...Service Manual 2017 8 51 51 5 Sealing tape door fixing for reversible door option ...