Toshiba 1112150201 (EN)

Model

RAS-(B)10UFV 

series

RAS-(B)13UFV 

series

RAS-(B)18UFV 

series

Power source

220–240V ~ 50Hz
220–230V ~ 60Hz

220–240V ~ 50Hz
220–230V ~ 60Hz

220–240V ~ 50Hz
220–230V ~ 60Hz

Maximum running 
current

8.5A

11.0A

12.0A

Plug socket & fuse 
rating

16A

Power cord

H07RN-F or 60245 IEC66 (1.5 mm

2

 or more)

Connecting cable

H07RN-F or 60245 IEC66 (1.0 mm

2

 or more)

Wiring Connection

1. Remove the valve cover, the electric parts cover and the cord clamp from 

the outdoor unit.

2. Connect the connecting cable to the terminal as identifi ed by the matching 

numbers on the terminal block of indoor and outdoor unit.

3. Insert the power cord and the connecting cable fully into the terminal 

block and secure it tightly with screws.

4. Use vinyl tape, etc. to insulate the cords which are not going to be used. 
    Locate them so that they do not touch any electrical or metal parts.
5. Secure the power cord and the connecting cable with the cord clamp.
6. Attach the electric parts cover and the valve cover on the outdoor unit.

Electrical Work

1. The supply voltage must be the same as the rated voltage of the air 

conditioner.

2. Prepare the power source for exclusive use with the air conditioner.

Packed valve handling precautions

  Open the valve stem until it touches the stopper. Once it is in contact with 

the stopper, refrain from applying any more force than is necessary.

  Securely tighten the valve stem cap with torque in the following table:

Evacuating

After the piping has been connected to the indoor unit, you can perform 
vacuuming together at once.

Using a vacuum pump

Be sure to use a vacuum pump with counter-fl ow prevention function so 
that inside oil of the pump does not fl ow backward into pipes of the air 
conditioner when the pump stops.
(If oil inside of the vacuum pump enters the air conditioner, which use 
R410A, refrigeration cycle trouble may happen.)

1. Connect the charge hose from the manifold valve to the service port of the 

packed valve at gas side.

2. Connect the charge hose to the port of the vacuum pump.
3. Open fully the low pressure side handle of the gauge manifold valve.
4. Operate the vacuum pump to start evacuating. Perform evacuating for 

about 15 minutes if the piping length is 20 meters (15 minutes for 20 
meters) (assuming a pump capacity of 27 liters per minute). Then confi rm 
that the compound pressure gauge reading is –101 kPa (–76 cmHg).

5. Close the low pressure side valve handle of the gauge manifold valve.
6. Open fully the valve stem of the packed valves (both gas and liquid 

sides).

7. Remove the charging hose from the service port.
8. Securely tighten the caps on the packed valves.

VACUUMING 

Evacuate the air in the connecting pipes and in the indoor unit using a 
vacuum pump. Do not use the refrigerant in the outdoor unit. For details, 
see the manual of the vacuum pump.

 

Tightening torque for connection of fl are pipe

  The pressure of R410A is higher than R22 

(Approx. 1.6 times). Therefore securely 
tighten the fl are pipes which connect the 
outdoor unit and the indoor unit with the 
specifi ed tightening torque using a torque
wrench. If any fl are pipe is incorrectly 
connected, it may cause not only 
a gas leakage but also trouble in the 
refrigeration cycle.

Flare at
indoor unit side

Flare at
outdoor unit side

Pressure gauge

Manifold valve

–101 kPa (–76 cmHg)

Handle Lo

Connecting pipe

Compound pressure gauge 

Vacuum 

pump

Handle Hi
(Keep full closed)

Charge hose
(For R410A only)

Vacuum pump adapter for 
counter-fl ow prevention 
(For R410A only)

Service port (Valve core (Setting pin))

Packed valve at liquid side

Packed valve at gas side

Charge hose
(For R410A only)

Hexagon wrench
is required.

Gas side
(

12.70 mm)

50 to 62 N·m
(5.0 to 6.2 kgf·m)

Gas side
(

9.52 mm)

33 to 42 N·m
(3.3 to 4.2 kgf·m)

Liquid side
(

6.35 mm)

14 to 18 N·m
(1.4 to 1.8 kgf·m)

Service port

14 to 18 N·m
(1.4 to 1.8 kgf·m)

4 mm

CAUTION

 

KEEP IMPORTANT 5 POINTS FOR PIPING WORK.

(1) Take away dust and moisture (inside of the connecting pipes).
(2) Tighten the connections (between pipes and unit).
(3) Evacuate the air in the connecting pipes using a VACUUM PUMP.
(4) Check gas leak (connected points).
(5) Be sure to fully open the packed valves before operation.

When using a multi-system outdoor unit is used, refer to the installation 
manual provided with the model concerned.

Stripping length of the connecting cable

Connecting cable

Power cord

Connecting cable

Power cord

Terminal 
block

Earth line

Connecting cable

Power cord

Connecting cable

Power cord

Terminal 
block

Earth line

RAS-10SAVR-A, RAS-18SAV-E

CAUTION

  Wrong wiring connection may cause some electrical parts burn out.

  Be sure to comply with local rule on running the wire from indoor unit 

to outdoor unit (size of wire and wiring method, etc.).

  Every wire must be connected fi rmly.

  If incorrect or incomplete wiring is carried out, it will cause an ignition 

or smoke.

  Prepare the power supply for exclusive use with the air conditioner.

  This product can be connected to the mains.

  Connection to fi xed wiring : A switch which disconnects all poles and 

has a contact separation of at least 3 mm must be incorporated in the 
fi xed wiring.

EN

ES

FR

IT

PT

PL

CZ

RU

CR

HU

TR

NL

GR

SV

FI

NO

DK

RO

BG

EE

LV

SK

SI

DE

8

Содержание 18UFV-E1

Страница 1: ...8SAV E RAS 3M26GAV E1 RAS 4M23SAV E RAS 4M27GAV E1 RAS 5M34UAV E AIR CONDITIONER SPLIT TYPE INSTALLATION MANUAL ENGLISH ESPAÑOL FRANÇAIS ITALIANO DEUTSCH PORTUGUÊS POLSKI ČESKY PУCСКИЙ HRVATSKI MAGYAR TÜRKÇE NEDERLANDS ΕΛΛΗΝΙΚΑ SVENSKA SUOMI NORSK DANSK ROMÂNĂ БЪЛГАРСКИ EESTI LATVISKI SLOVENČINA SLOVENŠČINA ...

Страница 2: ...enie Instalacji Rurowej Czynnika Chłodniczego 7 n Usuwanie Powietrza 8 n Podłączenie Okablowania 8 n Prace Elektryczne 8 INNE 9 n Próba Gazoszczelności 9 n Ustawianie Przełącznika Wyboru Pilota 9 n Ustawienia Przełącznika A B Wyboru Pilota 9 n Próba Działania 9 n Włączanie Funkcji Automatycznego Wznawiania Pracy Auto Restart 9 PL OBSAH BEZPEČNOSTNÍ OPATŘENÍ 1 SCHÉMA INSTALACE VNITŘNÍ A VENKOVNÍ JE...

Страница 3: ...talare Opţionale 3 UNITATE INTERIOARĂ 4 n Locul de Instalare 4 n Executarea unei Găuri şi Montarea Plăcii de Instalare 4 n Cum se Instalează Unitatea Interioară 5 n Instalarea Mascată 6 UNITATEA EXTERIOARĂ 7 n Locul de Instalare 7 n Măsuri de Precauţie privind Instalarea în Regiuni cu ninsori Abundente şi Temperaturi Scăzute 7 n Drenarea Apei din Unitatea Exterioară 7 n Racordarea Ţevilor de lichi...

Страница 4: ...s of charging port connecting sections on the main unit are different from those for the conventional refrigerant and different size tools are also required For connecting pipes use new and clean piping materials with highpressure withstand capabilities designed for R410A only and ensure that water or dust does not enter Moreover do not use any existing piping as its pressure withstand may be insu...

Страница 5: ...t enough or installation of the unit is improper the unit may fall and result in injury Electrical work must be performed by a qualified electrical engineer in accordance with the code governing such installation work internal wiring regulations and the manual A dedicated circuit and the rated voltage must be used Insufficient power supply or improper installation may cause electrical shock or fir...

Страница 6: ...If it is necessary to drain the defrost water attach drain nipple and cap water proof to the bottom plate of the outdoor unit before installing it Fixing bolt arrangement of outdoor unit RAS 10 13 18SAV Series 3 Batteries 8 Pan head wood screw 4 Remote control holder Do not allow the drain hose to get slack Make sure to run the drain hose sloped downward The auxiliary piping can be connected to th...

Страница 7: ...hole brim ring sold separately A place which provides the spaces around the indoor unit as shown in the diagram A place where there are no obstacles near the air inlet and outlet A place which allows easy installation of the piping to the outdoor unit A place which allows the front panel to be opened In case of block brick concrete or similar type walls make 5 mm holes in the wall Insert clip anch...

Страница 8: ... Do not form the drain hose into a wavy shape Do not put the drain hose end into water Do not put the drain hose end in the drainage ditch Drainage 1 Run the drain hose sloped downwards Wiring connection Wiring of the connection cable is necessary to remove the front panel 1 Remove the terminal cover and cord clamp 2 Insert the connecting cable according to the local rule into the pipe hole on the...

Страница 9: ...or more 20 to 30 240 to 250 Floor Wall Side view Unit mm 4 In case of lattice establishment Follow the following figure make sure to keep enough distance between lattice frame and wall Be sure to switch to wall burying mode The lattice should be make of wood Between the air inlet and outlet should be devided with partition board Be sure to establish the open part for RECEIVER The open part of latt...

Страница 10: ...A place full of machine oil A saline place such as the coast A place full of sulfide gas A place where high frequency waves are likely to be generated such as from audio equipment welders and medical equipment Strong wind Snow protection plate Snow protection hood At least 50 cm Snow accumulation line Holding frame Front Anchor bolts Install at least 50 cm above the snow accumulation line Do not u...

Страница 11: ...en fully the valve stem of the packed valves both gas and liquid sides 7 Remove the charging hose from the service port 8 Securely tighten the caps on the packed valves VACUUMING Evacuate the air in the connecting pipes and in the indoor unit using a vacuum pump Do not use the refrigerant in the outdoor unit For details see the manual of the vacuum pump Tightening torque for connection of flare pi...

Страница 12: ...ote Control by the tip of the pencil 00 will be shown on the display 2 Press during pushing B will show on the display and 00 will disappear and the air conditioner will turn OFF The Remote Control B is memorized Note 1 Repeat above step to reset Remote Control to be A 2 Remote Control A has not A display 3 Default setting of Remote Control from factory is A Unit B setup Press and hold MODE button...

Страница 13: ...1112150201 1 ...

Отзывы: