1600XP Series Quick Installation Guide

Inspection/Unpacking

Inspection

Upon receipt of the UPS, an inspection for shipping damage should be performed. Use caution when removing the unit from the 

pallet. Refer to labels or documentation attached to packing material.

Unpacking

Check the unit for loose, broken, bent or otherwise damaged parts. If damage has occurred during shipping, keep all original 

crating and packing materials for return to the shipping agent. The warranty does not apply to damage incurred during shipping. 

Ensure that the rated capacity and the model number specified on the nameplate conform to the order specifications.

Installation Precautions

Install  the  unit  in  a  well-ventilated  location;  allow  at  least  4  inches  (10  cm)  on  all  sides  for  air 

1. 

ventilation  and  for 

maintenance.

Install the unit in a stable, level and upright position that is free of excessive vibration.

2. 

Install the unit where the ambient temperature is within 32 – 104 °F (0 – 40 °C).

3. 

DO NOT install the UPS in areas that are subject to high 

4. 

humidity.

DO NOT install the UPS in areas that allow exposure to direct sunlight.

5. 

DO NOT install the UPS in areas that allow exposure to high levels of airborne dust, metal particles, or flammable 

6. 

gases.

DO NOT install the UPS in areas near sources of electrical noise. Ensuring a proper earth 

7. 

ground will reduce the effects 

of electrical noise and will reduce the potential for electrical shock.

DO NOT install the UPS in areas that would allow fluids or any foreign object to get inside the UPS.

8. 

The UPS generates and can radiate radio-frequency energy during operation. Although RFI noise filters are installed 

9. 

inside of the unit, there is no guarantee that the UPS will not influence some sensitive devices that are operating near 

by. If such interference is experienced, the UPS should be installed farther away from the affected equipment and/or 

powered from a different source than that of the affected equipment.

After ensuring that all power sources are turned off and isolated in accordance with established lockout/tagout procedures, 

10. 

connect the power source wiring of the correct voltage to the input terminals of the UPS.

Connect the output terminals of the UPS to the load (refer to NEC Article 300 – Wiring Methods and Article 310 – 

11. 

Conductors For General Wiring). Size the branch circuit conductors in accordance with NEC Table 310.16.

Conductor Routing and Grounding

Use separate metal conduits for routing the input power, output power, and control circuits.

1. 

Follow the wire size and tightening torque specifications listed on page 4.

2. 

Always ground the unit to reduce the potential for electrical shock and to help reduce electrical noise.

3. 

A separate ground cable should be run inside the conduit with the input power, output power, and control circuits.

4. 

THE METAL OF CONDUIT IS NOT AN ACCEPTABLE GROUND.

Operating Precautions

The UPS should not be used with a load that has a rated input that is greater than the rated output of the UPS.

1. 
2. 

DO NOT use the UPS to provide power to motors that require high starting current or with motors that require a long 

starting time, such as vacuum cleaners/machine tools (oversizing the UPS for lock rotor current would be required).

DO NOT attempt to disassemble, modify, or repair the UPS. Repairs and servicing should only be performed by Toshiba 

3. 

Field Service personnel.  

Access panels should be removed only by Toshiba Field Service personnel.

4. 

Turn the power on only after installing ALL of the covers.

5. 

If the UPS should emit smoke, produce an unusual odor, or make sound, turn the power off immediately.

6. 

Содержание 1600XP SERIES

Страница 1: ...orized to safely energize de energize ground lockout and tag circuits and equipment and clear faults 2 in accordance with established safety practices Be trained in the proper care and use of protective equipment such as safety shoes rubber gloves hard hats safety 3 glasses face shields flash clothing etc in accordance with established safety practices Be trained in rendering first aid 4 Be knowle...

Страница 2: ...UPS will not influence some sensitive devices that are operating near by If such interference is experienced the UPS should be installed farther away from the affected equipment and or powered from a different source than that of the affected equipment After ensuring that all power sources are turned off and isolated in accordance with established lockout tagout procedures 10 connect the power sou...

Страница 3: ...ba DO NOT add any additional jumpers Note 3 8 22 kVA UPSs have a jumper bus bar Output Terminal Connections Connect the load to the output terminals according the load voltage requirements See the Output Terminal Voltages table to the right Wire Size and Tightening Torque Use the following table to select the recommended wire size and terminal lug tightening torque for I O wire connections Item Te...

Страница 4: ...r MCCB to OFF Leave the UPS off until the DC bus is safely discharged approximately 5 10 minutes Restart the UPS by switching the main circuit breaker ON The table below summarizes the initialization parameters ID Command Options 111 Rated Vin Select from 208V 230V or 240V and press Write 215 Rated Vout Select from 208V 230V or 240V and press Write 141 Input Frequency Select from 60Hz or 50Hz and ...

Отзывы: