Autoped/ M10 APPENDIX rev 0 (09221 DRAFT)
A-31
Error No
Description
Cause
Elimination
Checking time
Reaction
E80 01
Continuous
routine
Malfunction
-----
Permanent
W
02
Power down then power up
F
E81 01
MCU routine
-----
Before: opening
Door/Gate
Closing Door/Gate
W
02
Power down then power up
F
E82 01
Dynamic
routine
Damping test failed
-----
After power down
then every 24hrs
when Door/Gate is
closing
W
02
Power down then power up
F
E83 01
Static routine
Motor current test failed
-----
Test occurs at the
door closed position
W
02
1. Power down then power up
again
2. If problem is not resolved, turn
the “ForceSlam potentiometer
adjuster” fully
counterclockwise.
3. If the problem still is not
resolved, replace the faulty
control and or motor operator.
F
Содержание AUTOPED 10
Страница 1: ...Autoped M10 APPENDIX rev 0 09221 DRAFT A 1 AUTOPED TM MODEL 10 OPERATOR APPENDIX 2021...
Страница 17: ...Autoped M10 APPENDIX rev 0 09221 DRAFT A 17 SECTION IV MENUS AND PROGRAMMING...
Страница 26: ...Autoped M10 APPENDIX rev 0 09221 DRAFT A 26 SECTION V TROUBLE SHOOTING AND ERROR CHARTS...
Страница 32: ...Autoped M10 APPENDIX rev 0 09221 DRAFT A 32 SECTION VI TERMINAL CONNECTIONS AND WIRING SCHEMATICS...
Страница 39: ...Autoped M10 APPENDIX rev 0 09221 DRAFT A 39 Fig VI 5 Secured Activation Devices...
Страница 40: ...Autoped M10 APPENDIX rev 0 09221 DRAFT A 40 Fig VI 6 Wiring for Double Door Gate System...
Страница 41: ...Autoped M10 APPENDIX rev 0 09221 DRAFT A 41 SECTION VII SERVICE PARTS...
Страница 42: ...Autoped M10 APPENDIX rev 0 09221 DRAFT A 42 VII 1 SERVICE PARTS COMPONENTS VISUAL GUIDE...