6
correct K Value.
Off_s
: Review your flow sensor’s documentation for its
correct Offset value.
PPG
(if Bermad selected): Pulse per gallon based on flow
meter wiring. See your Bermad flow meter documentation
for proper setting.
Rain Bucket Configuration
Tip
: The amount of water per tip. The typical rain bucket
might have a tip point of 0.01”. Check your rain bucket’s
documentation for correct tip point.
Max
: This is the limit at which the alarm will trip. If the
Tip unit is 0.01 inch, and the Max limit is 1 inch, it would
take 100 tips (within the R_win window) to trigger the
alarm.
Unit
: Select either English or Metric for display of rain
bucket data in either inches or millimeters.
Alarm
: On or Off. Turn on the alarm
R_win
: Set the period of time (as a moving window)
that the controller will calculate rain bucket tips towards
reaching the max limit.
Act
: If an alarm is triggered, this is the Action that the
controller will take. Possible choices are:
• None
. The alarm will only alert the operator.
• Start Station
. Starts a specified station.
• Cancel Station
. Cancels a specified station.
• Cancel All
. Cancels all irrigation activity.
• Rain Hold
. Places a rain hold on the controller for a
specified number of days.
Count
: The number of times the rain bucket has filled and
“tipped”, independent of Alarm status and R_Win setting.
Hr
: Possible to go back in hour increments to review the
number of tips during that hour from the current time.
H_Cnt
: The number of tips in that hour.
Total
: The number of times the rain bucket has filled and
“tipped” in the rain window (R_win above) only when the
alarm is set to On.
Status Sensor Configuration
Sw
: Normally Closed or Normally Open.
Select the correct setting for your sensor.
Alarm
: Turn the alarm On or Off for the sensor.
QTime
: Qualification time. How long does the alarm
condition (normally closed becoming open, for example)
have to stay in that condition for the alarm to be triggered.
RTime
: Reset time. Clears the alarm automactially if alarm
condition no longer exists for that period of time.
Act
: If an alarm is triggered, this is the Action that the
controller will take. Possible choices are:
• None
. The alarm will only alert the operator.
• Start Station
. Starts a specified station.
• Cancel Station
. Cancels a specified station.
• Cancel All
. Cancels all irrigation activity.
• Rain Hold
. Places a rain hold on the controller for a
specified number of days.
Input : 3 Typ:RAIN
Tip : 0.01 in
Max : 01.00 in
Unit : English (in)
Alarm : On
R_win : 24hr
Act : Rain Hold
Hold : 02days
Count : 4
Hr: 02 H_Cnt:00001
Input : 4 Typ:STAT
Sw : Norm Close
Alarm : On
QTime : 10s
RTime : 01m
Act : Cancel All