Toro LSSS Скачать руководство пользователя страница 5

4

Flow / Rain Bucket / Status 
(Normally Open / Normally 
Closed) Sensor

Secure the flow / rain bucket / status 

sensor’s 

black lead to screw IN 2 (or any 

terminal input thru IN 6) and red or 

white lead to terminal input 12V (see 

illustration)

.

DO NOT ATTACH A LEAD 

TO THE G (ground) 

TERMINAL. That will 

short the power to 

the controller.

Temperature Sensor

A temperature sensor must be connected to the 

Temperature Probe Connection port. See 

Sensor Input 

Board Overview

 on page 1 for port location.

The Toro temperature sensor will be available in late 2017.

Procedure

1. 

Return power to the controller. 

2.  The controller can automatically tell if a pressure 

sensor and/or a temperature sensor is installed. For 

flow, rain, and status sensors, however, we need to tell 

the controller what kind of  sensor has been installed 

on that terminal.

3.  Press the 

 

Station Settings

 button. 

 counter-clockwise to quickly get to the 

 

Sensor Setup Menu

.

4. 

Use the arrow keys to navigate to 

Input

 to select the desired input terminal.

5. 

Use the arrow keys to navigate to 

Typ

 to select the correct sensor type.

Pressure Sensor Configuration

Min

: Minimum pressure permitted for operation.

Max

: Maximum pressure permitted for operation.

Unit

: Select English or Metric for display of  pressure in 

pounds per square inch (psi) or bar.

Alarm

: Select either a high limit alarm (Hi) or a low limit 

alarm (Lo). In the 

Set

: field, it is possible to turn the Hi or 

Lo alarm On of  Off.

QTime

: Qualification time. How long does the alarm 

condition (max pressure exceeded, for example) have to 

stay in that condition for the alarm to be triggered. 

RTime

: Reset time. Clears the alarm automactially if  

alarm condition no longer exists for that period of  time.

Act

: If  an alarm is triggered, this is the Action that the 

controller will take. Possible choices are:

•  None

. The alarm will only alert the operator.

Sensor Setup Menu

Board Slot 8

Input : 2   Typ:

FLOW

I_WTW : 12:00am

O_WTW : 11:59pm

I_Min : 00000 9pm

Input : 1   Typ:PRES

Min   : 0000 psi

Max   : 0080 psi

Unit  : English(psi)

Alarm : Hi  Set: On

QTime : 010s

RTime : 002m

Act   : Cancel All

PType : 150 psi max

FLOW 1”

1      2      3      4      5      6      G   12V

!

Sensor configuration can either be done at the satellite in Local Mode or at a Central computer 

running Lynx. If communication is established between a satellite and a Lynx system, the Lynx 

system 

will overwrite all locally defined sensor configuration information

. Meaning, if operating a 

Lynx system, the sensors must be configured with Lynx. 

Sensor Configuration - Local Mode

Содержание LSSS

Страница 1: ...SHEET Rev ECM No Description of Change Drafter Date Approved By A 5121941 Release to rev A Richard Keightley 01 24 2017 Dat Nguy B 5124824 Sensor configuration and data review added for both Local Mod...

Страница 2: ...rating in Central Mode or locally when in Local Mode Sensor data is stored in the satellite for 12 hours and transmitted back to Lynx every 2 hours Current sensor information and alarm status can be v...

Страница 3: ...2 Apply the sensor sticker B to the sensor sticker area 3 Use a black marker to black out the sensors that are NOT part of the system 1 Remove the front panel door and power down the satellite contro...

Страница 4: ...ntation that shipped with your sensor These instructions assume the specified sensor is already installed in your irrigation system and cables already run to the controller For all sensor installation...

Страница 5: ...ed for operation Max Maximum pressure permitted for operation Unit Select English or Metric for display of pressure in pounds per square inch psi or bar Alarm Select either a high limit alarm Hi or a...

Страница 6: ...et a time when irrigation is no longer permitted I_Min For standalone Minimum flow rate allowed at the beginning of the water window I_Max Paired with I_Min Maximum flow rate allowed during the water...

Страница 7: ...er of days Count The number of times the rain bucket has filled and tipped independent of Alarm status and R_Win setting Hr Possible to go back in hour increments to review the number of tips during t...

Страница 8: ...Down arrow to Reset SIB s 3 to change to Yes All 4 There is a confirmation screen Press the Stop button to cancel the reset Firmware Version A handful of satellites will need a firmware update to tak...

Страница 9: ...1 we have one of each type of sensor installed with minimum and maximum values set 5 Remember a sensor input board takes up 8 stations and includes 8 stations We have to tell Lynx that the correct sat...

Страница 10: ...ration Reviewing Sensor Data It is possible to review sensor information in realtime or historically Realtime Click Utilities then Sensor Dashboard Select the Sensor Input Board to monitor You will se...

Страница 11: ...that may cause undesirable operation This equipment generates and uses radio frequency energy and if not installed and used properly that is in strict accordance with the manufacturer s instruction ma...

Отзывы: