Installation 

 
Tornatech Jockey Pump Controllers are built to NEMA industrial standards and are UL listed. These controllers 
are intended for use with fire pump systems. 
Except in some cases, the controller is also seismic approved and has been tested in accordance with the ICC-ES 
AC156, IBC 2015 & CBC 2013 standards. Proper installation, anchoring and mounting is required to validate this 
compliance report. Refer to this manual and drawings to determine the seismic mounting requirements and 
location of the center of gravity (you may need to contact factory). The equipment manufacturer is not responsible 
for the specification and performance of anchorage systems. The structural engineer of record on the project shall 
be responsible for anchorage details. The equipment installation contractor shall be responsible for ensuring the 
requirements specified by the structural engineer of record are satisfied. If detailed seismic installation 
calculations are required, please contact the manufacturer for the performance of this work. 
Jockey pumps are small, motor driven pumps used in conjunction with main fire pumps to compensate for minor 
leaks in the fire protection system and automatically maintain stand-by pressure. This reduces wear on the main 
pump and controller caused by unnecessary, frequent operation. 
 
  

Procedure (See corresponding steps in Technical Documentation) 

STEP 1 : IMPORTANT PRECAUTIONS 

Prior to mounting the controller and making any field connections: 
1. Verify that the following information is compatible with other related equipment on the project:  
• Controller rating label informations (AC line voltage, phase and frequency) 
• Motor horse power, voltage, phase and frequency 
• System pressure 
2. Open the door of the enclosure. After removing the cardboard protections, inspect the internal 
components and wiring for any signs of frayed or loose wires or other visible damage. 
 

STEP 2A : MOUNTING 

Consult job plans to determine the controller mounting location. For seismic applications, mounting arrangement 
should be rigid wall only. The structural engineer of record on the project shall be responsible for anchorage 
details. 
Tools and materials (wall mounting) required: 
• Assortment of common hand tools of the type used to service electromechanical equipment 
• Drill for drilling wall anchor holes 
• Hand level 
• Tape Measure 
• Four anchors with bolts and washers, per enclosure 
 

STEP 2B : ELECTRICAL CONNECTIONS 

All field connections and AC wiring are brought into the enclosure through the bottom or top conduit entrances. 
Refer to the National Electrical Code, the local electrical code or any other authority having jurisdiction for proper 
conduit entrance location. Use a hole punch, not a torch nor a drill, to punch a hole in the enclosure for the size 
conduit being used. Pull all wires necessary for field connections, remote alarm functions, AC power and all other 
optional features. Allow enough excess wire inside the enclosure to make up connections to the appropriate line, 

Содержание DJP

Страница 1: ...1 INSTALLATION AND MAINTENANCE MANUAL FOR JOCKEY PUMP CONTROLLERS ...

Страница 2: ...2 3 Technical Documents 2 Installation 1 Introduction Table of Contents JP Manual EN ...

Страница 3: ...Contents 4 Introduction 4 Types of Jockey Pump Controllers 4 Methods of starting stopping 5 6 Installation 6 Preventive maintenance and test 8 VISUAL INSPECTION 9 OPERATIONAL INSPECTION 9 10 Technical Documents 10 ...

Страница 4: ...main pump and controller caused by unnecessary frequent operation Types of Jockey Pump Controllers JOCKEY PUMP CATALOGUE NUMBER MODEL n EXAMPLE JP3 460 2 3 60 Model Prefix JP3 Voltage 460 V HP Rating 2 HP Phase 3 Frequency 60 Hz MODEL JP This jockey pump controller with across the line starter is specifically designed to the control jockey pump that maintains the designed water pressure in fire pu...

Страница 5: ...ances and eliminates unnecessary starting of the fire pump with all associated consequences i e high power drain load shedding undesirable alarms The presence of a 100 standby jockey pump associated with a circuit that alternates lead standby jockey pumps each time provides full back up and easy maintenance of the system any pump can be manually selected as lead Methods of starting stopping METHOD...

Страница 6: ...TANT PRECAUTIONS Prior to mounting the controller and making any field connections 1 Verify that the following information is compatible with other related equipment on the project Controller rating label informations AC line voltage phase and frequency Motor horse power voltage phase and frequency System pressure 2 Open the door of the enclosure After removing the cardboard protections inspect th...

Страница 7: ... to NFPA20 The water connection is on the bottom of the controller DANGER HAZARDOUS VOLTAGE IS PRESENT IN THE ENCLOSURE WHICH WILL CAUSE SEVERE PERSONAL INJURY OR DEATH MAINTENANCE OR START UP SHOULD BE PERFORMED ONLY BY EXPERIENCED LICENSED ELECTRICIANS ONLY QUALIFIED PERSONNEL SHOULD WORK ON OR AROUND THIS EQUIPMENT STEP 7 POWER ON AND SET IPD BOARD The front door mounted IPD membrane is describ...

Страница 8: ...configuration mode The controller will start if the START button is pressed Use the LEFT RIGHT buttons to navigate between the parameters Press the ENTER CONFIG button to select a parameter This will display the current value Use the UP DOWN buttons to change the selected parameter value The speed of the changing values will accelerate if the buttons are maintained Press the ENTER CONFIG button to...

Страница 9: ...ck for leaks on pressure transducer and piping Inspect door for proper alignment and function of door locks Inspect tightness of all connections Inspect tightness of all terminal jumpers Inspect controller grounding Inspect relays contactors and timers for any evidence of damage Inspect motor contactor power contacts Inspect tightness of all mounting nuts and screws OPERATIONAL INSPECTION YES NO C...

Страница 10: ...10 Technical Documents ...

Страница 11: ...11 ...

Отзывы: