TOPVERT S1 Series
E-
3
STANDARD SPECIFICATIONS
Series
TOPVERT S1 series
High performance general purpose micro drive
Output frequency range
0.1 - 600Hz, Programmable
Overload endurance
150% of rated current for 1 minute/10 minutes, Ta <=40, 200% of rated current for 2 seconds
Maximum output voltage
Proportional to Input Voltage, 3-Phase output
Power factor/Efficiency
Power factor no lower than 0.95. Efficiency no lower than 95% at full load
Control system
SPWM (Sinusoidal Pulse Width Modulation) vector control, 2 control modes :V/F, SVC
Speed control range
V/F mode 20:1; SVC mode 120:1
Output frequency resolution
Analog input: 10Bit(1/1024), Digital input: 0.01Hz, Fly-Shuttle dial input: 0.01Hz
Output frequency accuracy
Analog input: Within ±0.2% of max. output frequency (25
℃
±10
℃
).
Digital input: Within 0.01% of set output frequency
PWM carrier Frequency
0.7 -18kHz, Adjustable (Some models are limited)
Torque characteristics
auto-torque boost, auto-slip compensation; starting torque can be 150% at 1.0Hz
Skip frequency
Setting range 0.00 -600Hz, Max. 6 points, skip width are adjustable
Accel/Decel time
0.1-60000 seconds ( 2 Independent settings for Accel/Decel Time)
Stall prevention
0 to 250% of Rated Current, independent adjustable both in acceleration and constant speed operation.
DC Braking
DC Braking both when start up and stop , Braking Current Level: 0 to 125% of rated output current. Braking time: 0
to 60 seconds. Braking Start-Point when stop: 0.1-600Hz
Dynamic braking
Braking torque Approx. 20%(10%E.D.)
Control Cha
racte
ristics
V/F Pattern
2 of adjustable Random V/F curve. Constant Torque curve & Reduced Torque curve are available.
Keypad
By an Encoder style Fly-Shuttle dial. (setting resolution 0.01Hz/0.1Hz/1Hz/10Hz adjustable)
Frequency Setting
External
Signal
0 ~ +10VDC((Input impedance 20k
Ω
), 4 ~20mA DC ((Input impedance 250
Ω
),Multi-Function Inputs 1 ~2 (15 Steps
up/down), PLC run, RS-485 port MODBUS protocol
Keypad
Set by RUN and STOP. Switch-able between Keypad and External signal
Operation Setting
External
Signal
2 wire control(FWD/STOP
、
REV/STOP
、
RUN/STOP
、
FWD/REV), 3 wire control, FWD, REV, MI1 to MI2 can be
combined to offer various modes of operation, RS-485 serial interface MODBUS protocol
Multi-Function Digital Input
(DI)
(2 terminals)
Multi-step selection 0 to 15, first to second accel/decel switches, accel/decel inhibit, Input the counter, Pause Stop,
EF Input, Emergency Stop, auxiliary motor control is invalid, ACI/AVI speed command selection, Reset, PLC Run,
Up/Down command, Parameter team selection…etc, up to 43 functions.
Multi-Function Output Indication
(DO)
(1 indication )
Include a form C relay contact, a form A relay contact and 2 Open collector output. They can be programmed to
below indications: Drive Operating, Frequency Attained, zero speed, Base Block, Over torque,
Fault Indication, Local/Remote indication, PLC Operation indication, and Auxiliary Motor Output, Drive ready for
use, IGBT over-heat indication …etc, up to 63 functions.
Multi-Function Analog Input
(AI)
AVI: 0 ~ +10VDC((Input impedance 20k
Ω
), AU, ACI: 4 ~20mA DC ((Input impedance 250
Ω
). 2 different Input
terminals can be programmed to 15 functions
Fault Indication
The output will be activated when faults occur (User may get 1 or up to 4 indications from below terminals:1 Relay
contact point RA, RB, RC. or 2 Open-collector
O
PER
A
T
ING
Character
istics
Communication function
RS-485 serial port, MODBUS protocol, ASCII & RTU. (Baud rate up to 125 k bps)
Other Functions
PID feedback control, Flying start, Automatic voltage regulation (AVR), 2 accel./decel time selection , Auto-optimum
accel./decel. Time, S-curves, External fault interlock, External fault reset, Auto Restart after fault, 16 Fault records,
Automatic energy–saving, Upper/Lower limit, Programmable pulse output, Password protection, Pump and Fan
process control, Sleep/Wakeup function , Auto-Tuning, By-Pass, Y-Delta control,. Bi-Directional Speed search,
Reverse inhibit, Automatic torque boost & slip compensation, 16-step PLC run, 16 step preset speed, Coast or ramp
to stop, Random V/F curve, Mechanical brake release control, IGBT/ Heatsink temperature display & Pre-warning,
Quiet operation mode (No noise), User define Multi-function display, Over torque detection, Over current/voltage t
stall prevention, Sink/Source (NPN/PNP) mode, Electronic Thermal Relay, Internal Counter, DC injection brake both
in start and stop, Dynamic brake, Controlled cooling Fan, Removable keypad operator, Programmable
Multi-Function DI,DO,AI,AO and Ry terminals.
Intelligent Protection Functions
Self-testing, AC source Over Voltage, Phase loss, Over Voltage, Over Current, Under Voltage, Over Torque,
External Fault, Motor over-load, IGBT Over-temperature, Heat-sink Over-temperature, Electronic thermal, Ground
Fault, Output short circuit, Stall Prevention, Fuse protection, IGBT short circuit , Drive Over Load , DC bus capacitor
life monitoring, Auto carrier frequency adjust according temperature, 16 Trip records, Run information of
latest Fault
such like
DC-BUS voltage, Output voltage/Frequency/Current, Command frequency, IGBT temperature, Heat-sink
temperature….etc.
Digital Keypad
Eight Function keys:
Access Run, Stop, Reset/ Digit Shift, Display mode, Keypad Enable, Programming data
and…etc.
One Encoder style Fly-Shuttle dial:
Sets the parameter number and changes the numerical data
One 6 digits 7 segment display:
Display the Setting frequency/actual operation frequency, Output
current/Voltage, motor speed, Fault trip User defined unit(up to 88 type)…etc.
Six LED Display for status indication:
Display the Drive run/stop status, Forward/Reverse run status, Keypad
enable, and Frequency command source.
One RJ-45 connector:
Removable Keypad, remote control distance up to 150 meters.
Certificate
Complies with CE (EN61800-3) standard
Temperature
Ambient: -10 ~ +40 /(
℃
℃
-10 ~ + 50 ) (
℃
℃
Non-Condensing and not frozen). Storage: -20 ~ +60
℃
℃
Humidity
Below 98
%
R.H. (Non-Condensing)
Vibration
Below 20Hz: 1G, above 20Hz: 0.6G
Environment
Installation Location
Altitude 1,000 m or lower, keep away from corrosive gasses, liquid and dust
*TOPVERT all series are designed and manufactured base on CNS and IEC, IEEE, CE & UL standard.