8. CHECK AND ADJUSTING
58
Checking Calibration
1
Turn ON the power for the LS-80L and move
into high precision mode.
2
Install the LS-80L on a beam 10 meters or
higher above the floor, as shown in the diagram.
3
Hang the plumb bob from the LS-80L indicator
to the floor (Point A).
4
Mark the standard line on the floor perpendicular to
the direction of the beam where Point A crosses.
5
Set up the RL-SV1S for vertical rotation at the
position shown in the diagram and turn ON the power.
6
Maintain the level of the standard line on the
floor and laser beam, and move the RL-SV1S to
the direction of the arrow.
Ensure that the laser beam is at the LS-80L
indicator position (check with the buzzer sound
from the LS-80L).
8.2 Vertical Calibration
Level sensor
Beam
Approx.10m
Standard line
Laser beam
Approx.10cm