31
STARTUP
Step 10.
Start the system
When all installation requirements are met, the ECO-ClimaTEC is
ready to be started up. Be sure to check if there is no leakage at the
liquid connectors of the entire system. Do also check if all actions
and requirements of this manual are met.
If everything has been checked the main power supply can be
turned on and the ECO-ClimaTEC can start cooling/heating.
Before and after the startup there are a couple of items that should
be checked:
1.
Make sure the main power is ready to be started.
2.
Check the liquid level in the reservoirs after the ECO-
ClimaTEC has been operative for one hour.
3.
Check again if there is no leakage at the couplings after an
hour of operating time.
When all installation and start-up checks are succesfully done, the
ECO-ClimaTEC is ready for use.
OPERATING TEMPERATURE CONDITIONS
Operating temperature range of a system filled with:
Be aware of the reduction of the efficiency of the ECO-ClimaTEC
when using MEG (Mono Ethylene Glycol) because of its lower
thermal conductivity.
Water (˚C)
MEG 20% -10 (˚C)
MEG 40% -26 (˚C)
Hot side out max.
50
50
50
Cold side out min.
5
-5
-21
ambient BMCS max.
40
40
40
ambient BMCS min.
5
-5
-21