vii
eMC Wiring Guidelines
Cable routing
It is recommended that the power and signal cables for ICR actuators be routed as
far apart as possible to minimize system noise.
NOTE!
The standard cables from Tolomatic are not flex rated and have a minimum
bend radius of 3.75 inches. Any repeated flexing or excessive bending can result in
broken conductors and intermittent faults.
Shielding and grounding
When cabling the system, shielded cables are recommended. The standard cables
provided by Tolomatic have an overall shield with drain wires and the case ground
of the actuator is tied to a pin on the power connector. To minimize EMI and ensure
system reliability, all shield drain wires from all cables should be tied to a common
earth ground.
Proper and Safe Use of Product
Protection circuits and external fuses
A fuse should be added to the input power line to protect the actuator and power
supply from any potential over current conditions that may occur. In addition, if
regenerative energy will be present (especially in vertical applications), a means
for protecting against over voltage conditions should be implemented with a shunt
regulator or sufficient bulk capacitance.
Fail Safe e-Stop Recommendations
A means for a fail safe e-stop is highly recommended to ensure equipment and
personal safety. The e-stop should provide a means to remove main power from the
actuator to cease and prevent any unwanted motion.
device damage Prevention
To prevent permanent damage to the device, proper care should be taken not to
exceed published voltage, current, temperature, and load ratings. In addition, proper
wiring should be verified and safety measures checked before applying power.
H E A L T H A N D S A F E T y R E G U L A T I O N S
WARNING!
The manufacturer takes no
responsibility whatsoever
if the equipment is
modified or if the
equipment is used in any
way beyond performance
specifications.
Unauthorized modifications
or changes to the
equipment are strictly
forbidden and voids all
warranties.