Doc# 16302
Press Pilot 150 Manual
Page 39
_
Message Code 36 & 136 – PROX CYCLED AND NO UP ZONE
This fault occurs when the prox check cycles normally, but Bcam and
Tcam did not overlap at the bottom of the stroke. It can also be the
case that Tcam never cycled before the prox check cycled. Check to
make sure that the cams are working properly and the windows are set
correctly. Press the PP150 reset button to reset the fault.
Message Code 37 & 137 – BCAM OFF BEFORE TCAM CAME ON
Bcam and Tcam need to be set so that the degree Bcam turns off, and
the degree Tcam turns on overlap. If this does not happen, this fault
will occur. Refer to Chapter 2 Section xiii for a graphical illustration
on default settings for cam switches. Press the PP150 reset button
to reset the fault.
Message Code 38 & 138 – PROX CYCLED TWICE FAULT
In the cam based system, the prox check needs come on and off once
during the degrees that Tcam is off, and Bcam turns on. If for any
reason the prox cycles more than once in that window, this fault will
occur. Check the coupling on the cam box, and make certain the prox
switch is not cycling twice at the top. Adjust the prox as needed.
Press the PP150 reset button to reset the fault.
Message Code 39 & 139 – Ethernet heartbeat fault
When Ethernet is enabled, a heartbeat signal is checked between the
pp150 and the plc. This is considered a communications error on the
Ethernet network. Check all Ethernet cables.
Message Code 40 & 140 – Hydraulic OL Flt…Reset to Ack
When the Hyd. OL input goes on/off (depending on settings), this fault
will show on the screen. Push PP150 reset button to ack. The fault,
then follow the prompts. See hyd. OL section (16) for complete
process.
THE FOLLOWING MESSAGES (41-60) ARE CONSIDERED PROMPTS AND
NOT FAULT CONDITIONS. AFTER THE CONDITION STATED IS MET, THE
PP150 WILL AUTOMATICALLY RESET.
Message Code 41 & 141 – SINGLE STROKE READY
This is a prompt from the PP150 indicating that all requirements to be
able to run the press in Single Stroke mode have been verified.
Message Code 42 & 142 – CONTINUOUS NOT ARMED
This is a prompt indicating that all requirements to run in Continuous
mode are met except the Continuous Arm (prior action) button has not
been pushed. Push the Continuous Arm button to Arm the press. Once
the button has been pushed, the Press will stay armed for a user
defined time limit. Once the time is up, the button will need to be
pushed again.
Содержание Press Pilot 150
Страница 1: ...Toledo Integrated Systems Toledo Transducers Inc Press Pilot 150 Manual And Installation guide ...
Страница 2: ......
Страница 4: ..._ Doc 16302 Press Pilot 150 Manual Page 2 ...
Страница 18: ..._ Doc 16302 Press Pilot 150 Manual Page 16 4 PRESS PILOT 150 SCREENS The pp150 screens have moved to sheet 100 ...
Страница 54: ..._ Doc 16302 Press Pilot 150 Manual Page 52 ...
Страница 55: ..._ Doc 16302 Press Pilot 150 Manual Page 53 ...
Страница 67: ..._ Input Word 3 Figure 11 4 Doc 16302 Press Pilot 150 Manual Page 65 Input Word 2 Figure 11 3 ...
Страница 68: ..._ Doc 16302 Press Pilot 150 Manual Page 66 Input Word 4 Figure 11 5 Input Word 15 Figure 11 6 ...
Страница 69: ..._ Doc 16302 Press Pilot 150 Manual Page 67 Input Words 4 40 Figure 11 7 ...
Страница 71: ..._ Doc 16302 Press Pilot 150 Manual Page 69 Output Word 1 Figure 11 10 ...
Страница 73: ..._ Doc 16302 Press Pilot 150 Manual Page 71 ...
Страница 83: ..._ Doc 16302 Press Pilot 150 Manual Page 81 Figure 16 5 Figure 16 6 ...
Страница 86: ......
Страница 87: ...MAIN RESOLVER ENCODER CAMS ...
Страница 88: ......
Страница 89: ......
Страница 90: ......
Страница 91: ......
Страница 92: ......
Страница 93: ......
Страница 94: ......
Страница 95: ......
Страница 96: ......
Страница 97: ......
Страница 98: ......
Страница 99: ......
Страница 100: ......
Страница 101: ......
Страница 102: ......
Страница 103: ......
Страница 104: ......
Страница 105: ......
Страница 106: ......
Страница 115: ...Doc 16302 Press Pilot 150 Manual Page118 Figure 8 Figure 9 ...