18
No
Character
Name
Description
Initial
value
Display conditions/Remarks
⑲
Process value
event output
1 and 2.
sensitivity
Set the sensitivity of the process value
event output 1 and 2.
Setting range: 0.0 to 999.9
℃/
0 to 999
℃/
or
Displays when
□
is
.
Select Time signals and event output 1
and 2.
ON Delay/OFF Delay Time
for each step
ON Delay/Off Delay Time
common for all steps
Time signal ON Time for
each step
Time signal ON Time
common for all steps
Time signal ON Time
Time signal ON Time
for each step
⑳
Event output
1 and 2.
Time Signal
functions
Time signal ON Time
common for all steps
Display when
□
is
.
See "Time Signal and End
Signal" on Page 7,for setting
and operation of Time Signal
functions.
Event output 1
2 Time Signal
On Time.
On Delay time
Set the Time signal ON Time.
Setting range: 0 - 99 hrs.59 min.
If select 2 for Time signal
function, set ON Delay Time.
Displays when
□
are
,
,
.
Event output 1
,2 Time signal
OFF Delay Time
Set the Time signal OFF Delay Time
Setting range: 0 - 99 hrs.59 min.
Displays when
□
are
.
Loop Abnormal
Event Output 1,2
Set the detecting Time for loop
abnormal event.
Setting range: 1 - 9999 sec.
Displays when
□
are
.
Run signal input valid/invalid .
Valid
Invalid
Selection of
RUN Signal
Displays in case of RUN signal
input option.
Set the Communication parameter.
□△○×
□
BCC check (change by
▼
key)
Invalid
Valid
△
Data length(to be
changed by
▼
key)
7 bit
8 bit
○
Parity(to be changed by
▼
key)
None
Odd number
Even number
×
Stop bit(to be changed by
▼
key)
1
Communication
parameter
2
Displays when Communication
option selected.
No
Character
Name
Description
Initial
Value
Display condition/Remarks