POWER SUPPLY MANAGER

VX-3150DS

Thank you for purchasing TOA’s Power Supply Manager.

Please carefully follow the instructions in this manual to ensure long, trouble-free use of your equipment.

1134

TOA Electronics Europe GmbH

Suederstrasse 282, 20537 Hamburg, Germany

1134-CPR-137

DoP 16-005

EN 54-4: 1997 + A1: 2002 + A2: 2006

Fire Detection and fire alarm systems - part 4: power supply equipment

Содержание VX-3150DS

Страница 1: ...er Please carefully follow the instructions in this manual to ensure long trouble free use of your equipment 1134 TOA Electronics Europe GmbH Suederstrasse 282 20537 Hamburg Germany 1134 CPR 137 DoP 1...

Страница 2: ...Installation 8 4 3 Affixing Declaration of Compliance EN 54 4 Standard 12 5 CONNECTIONS 13 5 1 Connecting the VX 3150DS to VX 2000 System 13 5 2 Connecting the VX 3150DS to SX 2000 System 14 5 3 Conn...

Страница 3: ...sconnect the battery and contact your nearest TOA dealer Make no further attempt to operate the unit in this condition as this may cause fire or electric shock If you detect smoke or a strange smell c...

Страница 4: ...and negative orientation when connecting the power supply cord Reversed polarity connections will cause damage to the system When the Unit is in Use Use the specified power supply unit for the system...

Страница 5: ...ecified value In automatic mode the unit performs battery check every 3 and a half hours When the DS LINK is connected to the VX 2000 system SX 2000 system or VM 3000 system the resistance measurement...

Страница 6: ...is the last one of connected units Switches 4 and 5 Set the upper limit value of the internal battery resistance and battery connection cable resistance to be monitored for fault detection Setting sw...

Страница 7: ...INK IN OUT DS LINK IN connector Connects to DS LINK connector of the VX 2000 system SX 2000 system or VM 3000 system DS LINK OUT connector Connects to DS LINK IN connector of a daisy chained unit Note...

Страница 8: ...battery terminal to prevent shorts between positive and negative terminals Cable end treatment To secure the connection between the battery terminal and cable be sure to use the cable of specified di...

Страница 9: ...occurs connect a resistor of 18 k 1 4 W parallel to the batteries Use the specified type of batteries and capacity When batteries are connected together in a series parallel arrangement the inter con...

Страница 10: ...G 6 AWG 4 AWG 2 AWG 0 AWG 1 0 80 cm each 130 cm each 190 cm each 275 cm each 20 cm 20 cm 20 cm 20 cm Length 2 m AWG Example of wire length Cable A Cable C Cable B VX 3150DS Battery connection terminal...

Страница 11: ...temperature changes when charging the battery It should be mounted on the side of one battery in between 2 batteries using the supplied thermal insulating sheet to avoid ambient temperature change the...

Страница 12: ...e g at the upper right side as shown below EN 54 4 VX 3150DS Rack AC POWER BATTERY IN POWER CONNECT CONDITION CHECK CHARGING EN 54 4 Sticker supplied with the VX 3150DS Affix only the upper part of t...

Страница 13: ...Y POWER IN 24V MAX 150A POWER OUT 1 2 3 4 5 6 7 POWER OUT 19 33V MAX 25A WARNING Take special care to prevent the battery from being shorted by misconnection of the battery cable If the shore occurs t...

Страница 14: ...ble is broken or power fails Note For DC power supply to each component it is possible to use either of POWER OUT 19 33 V MAX 5 A terminal or POWER OUT 19 33 V MAX 25 A terminal SX 2100AI SX 2100AO or...

Страница 15: ...MAX 25A WARNING Take special care to prevent the battery from being shorted by misconnection of the battery cable If the shore occurs the unit may fail OUT DS LINK 16 24V MAX 0 3A POWER OUT TEMPERATUR...

Страница 16: ...K terminal connections Connect the DS LINK terminal of the VX 3150DS to the DS Link terminal of the SX 2000SM or SX 2100AO The figure below shows a connection example when the VX 3150DS units are conn...

Страница 17: ...DS LINK RJ45 male connector AWG 6 AWG 0 1 0 VM 3240VA 3360VA From VX 3150DS From VX 3150DS From VX 3150DS Note Remove the short bar attached at the factory 230 V AC 220 V AC 50 60 Hz 230 V AC 220 V A...

Страница 18: ...called VP amplifier System including VM amplifiers only One VX 3150DS is required every 2 VM 3360VA 3360E amplifiers or 3 VM 3240VA 3240E amplifiers Below is an example showing that one VX 3150DS is u...

Страница 19: ...3 VM amplifiers No of VM 3360VA 3360E 1 2 3 4 5 6 7 8 9 10 No of VX 3150DS units 1 2 3 4 5 No of VM 3240VA 3240E 1 2 3 4 5 6 7 8 9 10 No of VX 3150DS units 1 2 3 4 VP 3504 x 2 CH That only 2 channels...

Страница 20: ...3 4 5 6 7 8 9 10 No of VX 3150DS units 1 2 3 4 5 No of VM 3240VA 3240E 1 2 3 4 5 6 7 8 9 10 No of VX 3150DS units 1 2 3 4 VP 3504 x 2CH That only 2 channels can be used when VP 3504 connect to VX 315...

Страница 21: ...e to prevent the battery from being shorted by misconnection of the battery cable If the shore occurs the unit may fail OUT DS LINK 16 24V MAX 0 3A POWER OUT TEMPERATURE SENSOR 8 IN POWER OUT POWER OU...

Страница 22: ...cable to a single terminal use a ferrule terminal with an insulation sleeve to crimp the cables because such cable conductors could become loose Recommended ferrule terminals for signal cables made b...

Страница 23: ...al AWG 18 AWG 14 0 8 2 0 mm2 Round terminal SX 2000SM SX 2100AI SX 2000AO SX 2100AO SX 2000CI SX 2000CO VX 3004F VX 3008F VX 3016F DC POWER IN 4P removable terminal plug AWG 10 AWG 8 5 5 8 0 mm2 Round...

Страница 24: ...e system power Step 1 Turn on the AC power source Step 2 Check the DIP switch s Switch 8 is OFF If not place it to OFF position Step 3 Operate the system normally DIPSW SETTING CHARGE CURRENT 11A 5 5A...

Страница 25: ...t Charging Circuit CHARGING Fuse 15 A NO Voltage Checker BATTERY CONDITION BATTERY POWER NC NC NC NC NO Battery Check Switch When battery voltage drops below the reference voltage AC IN Control Connec...

Страница 26: ...n the battery data sheets The maximum storage durations are Ambient temperature Maximum time before re charge Less than 20 C 12 months 20 C 30 C 9 months 30 C 40 C 6 months The production date is usua...

Страница 27: ...us terminal of the battery to the VX 3150DS check on correct polarity and fixation in the battery cable clamp at the VX 3150DS 2 Connect the minus terminal of the battery with the plus terminal of the...

Страница 28: ...arger error will be logged and the Charge LED extinguishes The temperature sensor must not be disconnected during charging of the battery because then the charging voltage becomes high causing the dan...

Страница 29: ...l fuse 15 A of the VX 3150DS blown Consult your TOA dealer Either or both fans do not operate Battery Fault Reasons of a battery fault indication 1 resistance increase at the contacts due to corrosion...

Страница 30: ...he contact resistance is excluded from the measurement Measure the voltage on each path it may contain a fuse Add these voltages and divide by 5 5 A current The result is the resistance When it exceed...

Страница 31: ...otal Applicable Battery Panasonic LC X1265PG APG 65 Ah LC XA12100P 100 Ah LC XB12100P 100 Ah Yuasa NP65 12 65 Ah NPL100 12 100 Ah Control Connector DS LINK IN OUT RJ45 female connector for connecting...

Страница 32: ...Minatojima Nakamachi Chuo ku Kobe Hyogo Japan Authorized representative TOA Electronics Europe GmbH Suederstrasse 282 20537 Hamburg Germany Warning This equipment is compliant with Class A of CISPR 32...

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ...URL https www toa jp 133 02 00250 03...