5.2.1. No priority control (DIP switch 3: OFF, DIP switch 4: OFF)
In this mode, priority control is disabled. (Factory default)
For example, closing the control input 2 while the control input 1 is closed causes
the control output 2 to close simultaneously while the control output 1 remains
closed.
Control inputs 3 – 32 operate in the same manner.
SETTING
ON
Control input 1
Closed (make contact)
Closed
Open (break contact)
Open
Control input 2
Control output 1
Closed
Closed
Open
Open
Control output 2
5.2.2. Terminal number-based priority (DIP switch 3: ON, DIP switch 4: OFF)
The smaller the terminal number of the control input, the higher the priority level.
For example, closing the control input 1 while the control input 2 is closed causes
the control output 2 to open.
Opening the control input 1 causes the control output 2 to close.
Control inputs 3 - 32 operate in the same manner. Latency of 100 ms is employed
in order to prevent two or more control outputs from turning ON.
SETTING
ON
Control input 1
Closed
Closed
Open
Control input 2
Control output 1
Closed
Closed
Closed
Open
100 ms
100 ms
Open
Control output 2
Control input 2 is disabled while the control input 1 is being closed. The control output 2 becomes closed
when the control input 1 is opened.
100 ms
Control input 1
Closed
Closed
Open
Control input 2
Control output 1
Closed
Closed
Open
Control output 2