3-5 The order of link usage.
After power is on, links are used in numerical order for each communication.
Remember this to help you when problems are found with specific links.
Remarks:
1. Be sure to avoid mistake at the time of DIP switch installation and No. 200
Programming since such mistake may lead to trouble later.
2. Be sure to make "No. 200 Programming" after "Programming Data Table"
(attached to this manual) is filled out. Keep the finished "Programming Data
Table" (Initial Checking Sheet for the System 133-21-083-9) as a part of
complete drawings for each installation.
3. TROUBLE SHOOTING
3-1 Check of ROM & NMOS-RAM - No calls on the system.
1. Put the 4 "LINK SELECT" switches of the HC upward (Link No. 15
SELECT) and switch on the AC power of the exchange.
2. If there is no error, the indication lamps will not light.
3. In the event of a memory error, the lamps may light as shown in the example
of Fig. 1.
4. The error indications will remain on until you use Link No. 15 for com-
munications.
3-2 Confirming of the CP normal working
If the CP, OC and HC are working normally, the HC's indication lamps of LINE
BUSY, LINE ADDRESS and SIGNAL CODE go out.
When any of the lamps lies alight, it is possible that any of the CP, OC or HC is
faulty.
Check first that the CLOCK lamp of the HC is lighting, then confirm that the
CP is working normally by hearing the clicking sound of the PI unit's relay which
is produced when the relay is activated through dial operation of the paging.
If the CP is found working normally, chances are that the HC is faulty, followed
by the OC.
3-3 Check of CMOS-RAM (Programmed data memory)
You hear calling tone instead of confirmation tone, if there is CMOS memory
error at the time of initial programming and registration using station No. 200,
or at the time of registration to Single Digit Number or Personal Number or
Remote Number.
3-4 Dial receiving test
1. Instead of the PI-62 unit, use the PIU-52A (a unit used in the EXES-5000
System) to check the dial receiving section of the CP also to check if the
signal is correctly transmitted as dialed from the station to be tested.
2. If you place all "LINK SELECT" switches (1 ~ 4) of SW-A on the CP-62 in
"OFF" position, conversation is impossible but the dial code from each
station is indicated on the LED's of the PIU as dialed. Use this to find the
cause of any fault of receiving dial information.
3. With use of the PI-62 unit fitted
with no LED, you can also
check that the CP receives the
dial signal by hearing the click
sound of the relay produced
when it is activated.
Fig. 2 DIP switches
(SW-A of the CP)
Example of
Hands-free/Handset Station
(HF-600M/S)
No. 1 and No. 2 out of 4 pcs
ROMs (2732) have "read"
error.
No. 0 and No. 1 out of 4 sets
of N-MOS RAMs(2114) have
"read" error.
(One set of RAMs consist of
2 ICs)
Indicate memory error.
LINK SELECT Switches set
to select No. 15
Fig. 3 Dial code indication
Example of
Handset Station
(TL-600M/S)
Example
Error ROM • RAM Chip No.
PIU-52A unit
— 7 —
Fig. 1
All manuals and user guides at all-guides.com