BOILER SYSTEM DIAGNOSTICS - Vacuum Switch - Optional
PROBLEM
POSSIBLE CAUSE
SOLUTION
Switch activated manually
Improper diaphragm movement Replace switch if improper diaphragm movement is detected.
Low water flow
Correct problems related to inadequate water flow.
Air leak in or punctured
diaphragm
Replace vacuum switch if diaphragm shows an air leak or
hole.
Switch shows continuity
when activated
Problem elsewhere insystem
If vacuum switch works properly, continue with other boiler
control diagnostics.
Switch does not shows
continuity when activated
Switch contact bad
Replace switch with another one.
BOILER SYSTEM DIAGNOSTICS - Thermostat
PROBLEM
POSSIBLE CAUSE
SOLUTION
Thermostat set improperly
Thermostat set too low
Set thermostat properly and ensure connections are not
loose or corroded.
Boiler fires when thermostat
jumped, but will not fire with
thermostat in circuit
Thermostat bad
Replace Thermostat.
Boiler will not fire when
thermostat jumped
Problem elsewhere insystem
Continue with boiler control diagnostics. If boiler still does not
fire, the thermostat may need
replaced.
BOILER SYSTEM DIAGNOSTICS - High Temperature Limit
PROBLEM
POSSIBLE CAUSE
SOLUTION
Electrical continuity through
switch
Connections loose or corroded
Check connections to high temperature limit switch to ensure
that they are not loose or
corroded.
Problem elsewhere in system
If there is continuity through the switch but the boiler still
does not fire, there is a problem
elsewhere in the system. Continue with boiler control
diagnostics.
No continuity through switch Switch bad
Replace switch.
BOILER SYSTEM DIAGNOSTICS - Low Fuel Shut-Off
PROBLEM
POSSIBLE CAUSE
SOLUTION
Fuel level low
Switch may be operating properly Add fuel and retest.
Fuel level proper
Level sensor stuck
Check level sensor for proper movement. Clear, repair, or
replace sensor assembly.
Reed switch bad
Check level sensor for proper action. Replace switch if
needed.
WWW.TMGINDUSTRIAL.COM
P33/41
Toll Free:1-877-761-2819
Содержание TMG-HW28
Страница 34: ...WIRING DIAGRAMS WWW TMGINDUSTRIAL COM P34 41 Toll Free 1 877 761 2819...
Страница 35: ...PARTS DIAGRAMS WWW TMGINDUSTRIAL COM P35 41 Toll Free 1 877 761 2819...
Страница 36: ...WWW TMGINDUSTRIAL COM P36 41 Toll Free 1 877 761 2819...
Страница 39: ...PUMP DIAGRAMS WWW TMGINDUSTRIAL COM P39 41 Toll Free 1 877 761 2819...