6
8
、
Note
!
Read this manual before using, to prevent the error operation
caused by the failure to Fully understand the operating
procedures, and retain the manual for ready reference.
( )
( )
1
Can not normally display measured values in the display window alternating show:
"orAL" character, indicating that the input of the measurement signal abnormalities or Out of
range; check Int parameter settings, and then the input sensor signals are the same category,
if it is determined the same, check the input sensing Signal not pick the wrong line, if it is
determined to not pick the wrong line, check whether the sensor problem, replace another
sensor to try.
2
The instrument used by the local environmental temperature and humidity can not
exceed the scope of the provisions, the instrument around should allow sufficient space for
CP
Control cycle
CP reflect the instrument operator to adjust the speed, the size of
the CP that affect the control accuracy.
With SSR, SCR output control cycle preferable to shorter, usually
0.5-3.0 Seconds. The relay switch output is generally in 15-40
seconds.
When the output relay switches , the CP will be limited to
3 seconds, And self-tuning At will automatically set the CP as the
appropriate value, taking into account the control accuracy And
mechanical switch life.
When the control mode CntL = onoF, the action of the CP as an
output disconnect or power-on output ON Delay time.
0
.
2
~
300.0
Int
Input Signal
Input spec:
K
、
E
、
J
、
N
、
Pt
(
Pt100
)
dp
Decimal
point
0 (no decimal), 0.0 (one decimal place).
InF
dU
SvL
SvH
-
9990
~
+
30000
SC
Input Shift
Adjustment
Sc is used to shift input to compensate the error caused by
transducer, input signal, or auto cold junction compensation of
thermocouple.
PV after compensation=PV before compen Sc It is generally
set to 0. The incorrect setting will cause measurement inaccurate.
-
1999
~
+
4000
PV
input filter
The value of InF will determine the ability of filtering noise.
When a large value is set, the measurement input is stabilized but
the response speed is slow. Generally, it can be set to 1 to 3.
If great interference exists, then you can increase parameter “InF”
gradually to make momentary fluctuation of measured value less
than 2 to 5.
When the instrument is being metrological verified, “InF” s can be
set to 0 or 1 to shorten the response time.
Temperature
unit selection
°C
:
°F
:
fahenheit equals
celsius equals
Low limit
of SV
Minimum value that SV is allowed to be.
Upper limit
of SV
Maximum value that SV is allowed to be.
0
~
40
°C
°F
HYS
Control
hysteresis
0
~
2000
HYS is used for on-off control to avoid frequent
on-off
action of relay.
For a reverse acting (heating) system, when PV > SV, output turns
off; when PV<SV-HYS, output turns on.
For a direct acting (cooling) system, when PV<SV, output turns off;
when PV>SV+HYS, output turns on.
Differential
time
No derivative effect when d=0
0
~
3200
seconds
d
heat dissipation, instrument internal temperature rise due to thermal radiation will lead to a
result of the measurement accuracy and service life of the affected. In this Case, to be taken
to a forced cooling fan or other measures to reduce the ambient temperature.
3
the extension or connection then the thermocouple leads should be used with the
thermocouple type to match the compensation conductor; extend or connect the
thermoelectric Resistance of the lead, you should use the minimal resistance of the wire and
cable away from power lines and load connection, in order to avoid signal interference.
( )
5
Guangzhou Tmcon Electronic Technology Co., Ltd.
R
Sales Hotline:
-
020 34273933
Technical Hotline:
020
-
34273900
Http://www.china-tmcon.com
Made in Guangzhou, China
0
0.0
Parameter code
*
*
solid state relay output type factory is set to ,
the relay contact output type factory set to .
factory setting
Parameter code
Parameter code
factory setting
factory setting
9
、
default settings.