background image

5

.

Panel Description

Upper display window

1

Lower display window

2

To the parameter key, the Enter key

3

Data shift key

4

Increase 

 key

the

5

Reduce the key

6

OUT Lamp

7

6

Display the status and basic operation

7

Parameter list and function

press and hold        key 2 seconds, LOC parameter appears, set the LOC = 800,Then press 
the        key to confirm and enter the system parameter setting state.

Parameter 
code

Meaning of 
parameters

Explain

Setting 
range

LOC

Parameter
lock

LOC<9000, will automatically for 0, allowed to modify  the SV Set 
Value.

LOC

9000, are not allowed to modify the SV Set Value.

Set the LOC = 800, then press         key to confirm, can enter the 
following system parameters.

0

~

9999

3

4

OUT

AUT

A L 1

TF800

TMCON

PV

SV

A L 2

1

2

3

4

6

7
8

5

PV

SV

Press          2 SEC

+

The next
 parameter

2 SEC

,

Return to the

 previous parameter

For example: 
measuring a value of 600.0
Set value 600.5

The basic display state

6

.

1

.

System parameter setting

PV

SV

LOC parameter 
appears

Set the LOC = 800,
Then Press

In

s

tr

u

m

e

n

t p
o

w

e

r

Access to the system parameter setting state

In the basic display state, press and hold        key 2 seconds, LOC parameter appears, set the 
LOC = 800,Then press the        button to confirm and enter the system parameter setting state.
        ,          ,         Key can directly modify the parameter values. Press the        key to reducing 
the data, press the        

 to increase the data,Waiting to modify the value of the decimal 

point will flash (like a cursor)

.

press key and hold, you can quickly increase / decrease in value, 

And the speed will be automatically accelerated. also press the         key to move to modify the 
data location (cursor), the operation is more efficient.        Key can be stored to modify 
parameter values and display the next parameter,press and hold        key 2 seconds,and can 
return to the previous parameter; 

 and hold        key and then press the        key can 

immediately exit the parameter setting state. 

key

press

6.2 Set Value Setting
In basal display status, if the parameter lock “Loc” isn't locked, we can set setpoint (SV) by 
pressing        first

then can press       ,        or        to adjust value. Press        key to decrease 

the value,        key to increase the value, and        key to move to the digit expected to modify. 
Keep pressing        or        , the speed of decreasing or inscreasing value get quick. The range 
of setpoint is between the parameter SPL and SPH.

6.3 “At”PID Parameter auto-tuning 
"At" parameter "OFF" is set to "ON" and then press the        KEy to confirm instrument can start 
the implementation of the auto-tuning  Given function,the instrument in the basic display state 
display will flash the word "At", the instrument after 2 oscillation cycle ON-OFF control can 
automatically calculate the PID parameters.If you want to advance to give up auto-tuning , "At" 
parameter “ON” is set to “OFF” and then press        key to confirm.
Given tuning parameter values obtained are not identical, to perform auto-tuning  function, 

9

AL1 

Lamp

8

AL2 

Lamp

9

should be first given value set in

 

The most commonly used value or middle value, if the system 

is good insulation properties of the furnace, the given value should be set in the system uses 
the maximum, and then

 

Execute the start of the operation of auto-tuning  function. Reasons to 

learn, auto-tuning  after the initial use, the effect may not be the best, you need a period of time
 (usually the same time auto-tuning  control) before they can get the best results.

AL1 high 
limit alarm 
value

AL1 low
limit alarm
value

-

999

~

+

32000

“HAL1” is the absolute value alarm or deviation value alarm, by

 

“ALtd” parameter definition.
When the value set to Max. will disable this function.(3200)

“LAL1” is the absolute value alarm or deviation value alarm, by

 

“ALtd” parameter definition.

When the value set to Min. will disable this function

.(-

999

)

AL2 high 
limit alarm 
value

AL2 low
limit alarm
value

“HAL1” is the absolute value alarm or deviation value alarm, by

 

“ALtd” parameter definition.
When the value set to Max. will disable this function.(3200)

“LAL1” is the absolute value alarm or deviation value alarm, by

 

“ALtd” parameter definition.

When the value set to Min. will disable this function

.(-

999

)

HAL2

LAL2

HAL1

LAL1

Alarm 
hysteresis

Alarm mode

Avoid frequent alarm on-off action because of the fluctuation of PV

ALtd=0

AL1is the 

is the 

.

deviation value alarm,AL2 

absolute 

value alarm
ALtd=1

AL1 and AL2 is the absolute value alarm.

ALtd=2

AL1 and AL2 is the deviation value alarm.

Control 
mode

onoF: on-off control. For situation not requiring high precision.
FPId: advanced artificial intelligence ”FUZZY PID“ control.

0

~

2000

0

~

2

OFF: close the 

 function.

ON: start a 

 function.

  finish will automatically returns to the OFF state.

auto-tuning

auto-tuning

auto-tuning

auto-tuning 

ON
OFF

onoF
FPId

onr: Reverse acting. Increase in measured variable causes a 
decrease in the output, such as heating control.
ond: Direct acting. Increase in measured variable causes an 
increase in the output, such as refrigerating control.

Selection of 
heating 
refrigeration

AHYS

ALtd

CntL

At

orEv

onr
ond

Proportional 
band

Integration 
time

No integral effect when I=0

1

~

32000

1

~

9999

seconds

Proportional band in PID and APID control. Instead of percentage 
of the measurement range, the unit is the same as PV.
Generally, optimal P, I, D and CP can obtained by auto tuning. They 
can also be manually inputted if you already know the correct 
values.

P

I

Отзывы: