CAUTION
If the exact steam pressure is not known:
To find out the exact pressure directly in front of the trap, it is best to install a pressure
gauge. If this is not possible, determine it as follows:
The TM is equipped with a function that selects the steam pressure equivalent to the
measured surface temperature and displays this value. If the steam pressure is
completely unknown, do not enter a steam pressure value. Simply press
ENT
after the
equivalent pressure value is displayed to proceed with automatic determination of the
trap judgement. Note that the surface temperature is not the actual internal temperature
of the trap, so the accuracy of the judgement will be slightly reduced.
NOTE:
It is possible to revise the value or redo the judgement after the pressure has been entered.
For more information, see "7.3 Re-judgement".