62
2. Connecting the power supply cable
(1) Open the cover of the control panel and pass
the cable through the control board from the
cable connector on the front left.
(2) Connect the power supply cable to the L, N
and E terminal blocks on the far left.
L, N: Power source
E: Ground
(3) When wiring the power cable or other cabling
from the unit elsewhere, make sure that the
unit cover can still be removed.
(Do not fix electrical conduits, etc. to the
cover.)
If the unit cover cannot be removed, unit
commissioning or maintenance may be
refused.
Wiring through
either back or top*
of the cover is
recommended.
Do not wire from the hole in the cove r.
If the cover cannot be removed,
commissioning and maintenance
cannot be performed
* For indoor
specification only
L
N
E L1 N1 L1 N1
PWR
Relay
Terminal
Grd
Standard models
Oceania models