172-65605M-14 (SQ2/SQ4/SQ6) 10 Dec 2019
23
Parameter Settings Screen
Parameter Settings Screen (1)
No.
Function
Description
1
High Temp (
°
C)
Sets the temperature at which the high temperature alarm
is triggered.
・
Defined as: Input value + set temperature = high temperature
alarm value(When the temperature is set to 70
°
C and upper
limit alarm set temperature is set to 10
°
C, the high
temperature alarm value becomes 80
°
C.)
・
When the water temperature falls below the alarm value during
an active alarm, the unit will recover from the alarm status.
・
Factory setting: 10
°
C
2
High Temp Alarm
Delay
Sets the alarm delay time for the high temperature alarm.
・
When the water temperature exceeds the value set in No. 1
(High Temp) for a longer time period than set in No. 2, an high
temperature alarm will be triggered.
(When the high temperature alarm value is set to 80
°
C and
alarm delay is set to 10 seconds, an alarm will be triggered if
the water temperature exceeds 80
°
C for more than 10
seconds.)
・
When the temperature falls below the high temperature alarm
value within the set alarm delay time, an high temperature
alarm will not be triggered.
・
Factory setting: 10 seconds
3
Low Temp (
°
C)
Sets the temperature at which the low temperature alarm is
triggered.
・
Defined as: Set temperature – input value = low temperature
alarm value.
(When the temperature is set to 70
°
C and the lower limit
alarm set temperature is set to 10
°
C, the low temperature
alarm value becomes 60
°
C.)
・
When the water temperature exceeds the alarm value during an
active alarm, the unit will recover from the alarm status.
・
Factory setting: 10
°
C
Continued on the next page
8
5
6
7
1
2
3
4
9