172-65126MA-10  (FLl5/FL21/FL32/FL5-C/FL21-C/FL32-C + BD2)  10  Mar 2017

 

Maintenance 

 

 

Take measures to prevent people from coming into direct contact with 

product outlets. Failure to do so may result in burns or other injury from 

the discharge of fluids.

 

CAUTION 

 

 

Be sure to use only the recommended components when repairing the 

product, and NEVER attempt to modify the product in any way. Failure to 

observe these precautions may result in damage to the product or burns 

or other injury due to malfunction or the discharge of fluids.

 

CAUTION 

 

Operational Check 

A visual inspection of the following items should be done on a daily basis to determine 
whether the trap is operating properly or has failed. Periodically (at least biannually) the 
operation should also be checked by using diagnostic equipment such as a stethoscope, 
thermometer, TLV Pocket TrapMan or TLV TrapMan. 

If the trap should fail, it may cause damage to piping and equipment, resulting in faulty or 
low quality products or losses due to steam leakage.   

Normal                         

:  Condensate is discharged continuously, together with flash steam, 

and the sound of flow can be heard. If there is very little 
condensate, there is almost no sound of flow. 

Blocked                     
(Discharge Impossible) 

:  No condensate is discharged. The trap is quiet and makes no 

noise, and the surface temperature of the trap is low. 

Blowing                       

:  Live steam continually flows from the outlet and there is a 

continuous metallic sound.   

Steam Leakage   

:  Live steam is discharged through the trap outlet together with 

condensate, accompanied by a high-pitched sound. 

(When conducting a visual inspection, flash steam is sometimes mistaken for steam leakage. For 
this reason, the use of a steam trap diagnostic instrument [such as TLV TrapMan if appropriate] in 
conjunction with the visual inspection is highly recommended.) 

 

 

 

Parts Inspection 

When parts have been removed, or during periodic inspections, use the following table to 
inspect the parts and replace any that are found to be defective. 

Procedure

 

Gaskets:   

Check for warping or scratches 

Screens:   

Check for clogging or corrosion 

X-element:   

Check for damage 

Valve Seat:   

Check for damage 

Body Interior: 
Valve Area on the 
X-element, Valve Seat: 

Check for build-up of scale 
Check dirt, oil film, wear and damage 

 

Clear, slightly 

bluish jet 

 

White jet 

containing 

water droplets 

 

Flash Steam 

Live Steam Leakage 

Содержание QuickTrap FL21

Страница 1: ...C FL32 C BD2 10 March 2017 Thermostatic Steam Trap QuickTrap FL5 FL21 FL32 FL5 C FL21 C FL32 C Trap Unit L5 L21 L32 L5 C L21 C L32 C For Connector Body F46 Copyright 2017 by TLV CO LTD All rights reserved Instruction Manual Instruction Manual ...

Страница 2: ...ared to conventional steam traps and also facilitates repair and maintenance operations This is a new type of valve mechanism in which a thermoliquid is sealed inside the X element and the valve opens or closes based on the difference between the saturation temperatures of the thermoliquid and the water The X element is very sensitive to changes in temperature and responds with great accuracy quic...

Страница 3: ...mbols Indicates a DANGER WARNING or CAUTION item DANGER Indicates an urgent situation which poses a threat of death or serious injury WARNING Indicates that there is a potential threat of death or serious injury CAUTION Indicates that there is a possibility of injury or equipment product damage CAUTION Install properly and DO NOT use this product outside the recommended operating pressure temperat...

Страница 4: ...which no freeze up will occur Freezing may damage the product leading to fluid discharge which may cause burns or other injury The pressure and temperature values displayed on the nameplate of the connector body are the values for the connector body itself and not for the entire trap Improper use may result in such hazards as damage to the product or malfunctions that may lead to serious accidents...

Страница 5: ...s a check valve TLV CK been installed 4 Is the inlet pipe as short as possible with as few bends as possible and installed so the liquid will flow naturally down into the trap 5 Has the piping work been done correctly as shown in the figures below Requirement Correct Incorrect Install catchpot with the proper diameter Diameter is too small Make sure the flow of condensate is not obstructed Diamete...

Страница 6: ...which it is mounted When a trap unit is installed on a connector unit and the PMA TMA and or PMO TMO values displayed on the two nameplates differ the specifications for the assembled products are restricted to the lower values Trap Unit Production Lot No Valve No Model Maximum Allowable Temperature TMA Nominal Diameter Maximum Operating Temperature TMO Maximum Allowable Pressure Maximum Operating...

Страница 7: ...the model name No Name M R T C No Name M R T C 1 Trap Body 11 Spring Clip 2 Connector Flange 12 Cover Bolt 3 Snap Ring 13 Trap Screen 4 Inner Outer Connector Gaskets 14 Connector Bolt 15 Connector Body 5 Valve Seat 16 Screen 6 Trap Cover 17 Screen Holder Gasket 7 Cover Gasket 18 Screen Holder 8 X element 19 Connector Nameplate 9 X element Guide 20 Flange 10 Nameplate 21 Check Valve Ball M Maintena...

Страница 8: ... blow out the inlet piping to remove any piping scraps dirt and oil Close the inlet valve after blowdown 3 Install the product so the arrow on the body is pointing in the direction of condensate flow 4 The connector body has no restrictions on installation orientation except for the following conditions the universal flange face for connecting to the trap unit must be in the vertical plane and the...

Страница 9: ...her with flash steam and the sound of flow can be heard If there is very little condensate there is almost no sound of flow Blocked Discharge Impossible No condensate is discharged The trap is quiet and makes no noise and the surface temperature of the trap is low Blowing Live steam continually flows from the outlet and there is a continuous metallic sound Steam Leakage Live steam is discharged th...

Страница 10: ...elow See Fig A Connector Gaskets Remove with a scraper and clean the connector flange with a soft tool Replace with new gaskets to facilitate assembly and prevent loosening of the gaskets apply a small amount of adhesive at 120º intervals around the outer edge of the gaskets Attaching the Trap Unit to the Connector Body 1 If attaching a new trap unit be sure to remove the protective cap from the c...

Страница 11: ...othly Trap Screen Remove without bending Insert without bending Cover Gasket Remove with a scraper without scratching the seating surface of the trap body Replace with a new gasket Make sure there are no pieces of the old gasket left on the sealing surfaces of the body and then reattach Table of Tightening Torques Part Name Torque Distance Across Flats N m lbf ft mm in Valve Seat 35 26 19 3 4 Conn...

Страница 12: ...nector Unit Cover Bolt T Trap Cover T Spring Clip T X element T Valve Seat T X element Guide T Trap Screen T Cover Gasket T Trap Body T Inner Outer Connector Gaskets T Screen C Connector Body C Screen Holder Gasket C Screen Holder C Connector Bolt T Connector Flange T Nameplate T Connector Nameplate C ...

Страница 13: ...e then press the gasket onto the center of the gasket surface of the plug holder making sure the anti seize affixes the gasket tightly to the plug holder Check to make sure the gasket is not caught in the recesses of the threads Hold the plug holder upside down to make sure that the anti seize makes the gasket stick to the plug holder even when the plug holder is held upside down Screw the plug ho...

Страница 14: ...here is insufficient pressure differential between the trap inlet and outlet Compare specifications and actual operating conditions Steam is discharged or leaks from the outlet blowing steam leakage There is rust or scale between the valve area on the X element and the valve seat Clean parts The X element valve and valve seat are damaged Replace with a new X element and or valve seat The X element...

Страница 15: ...unctions due to improper installation use handling etc by other than TLV CO LTD authorized service representatives 2 Malfunctions due to dirt scale rust etc 3 Malfunctions due to improper disassembly and reassembly or inadequate inspection and maintenance by other than TLV CO LTD authorized service representatives 4 Malfunctions due to disasters or forces of nature 5 Accidents or malfunctions due ...

Страница 16: ...n the BD2 valve or the BD2 valve seat in excess of the appropriate tightening torque Over tightening may cause breakage to threaded portions which may cause burns other injuries or damage CAUTION Do not excessively loosen the BD2 valve when opening the blowdown valve The valve stopper pin installed to prevent the BD2 valve from being removed may break and internal pressure may result in the BD2 va...

Страница 17: ... careful not to loosen the BD2 valve so far that it becomes removed from the BD2 valve seat If the valve stopper pin becomes damaged large quantities of steam will be discharged in a jet stream 3 Close the BD2 valve until the flow of fluid completely stops If the flow of fluid does not stop re open the BD2 valve as in step 2 to blow out any scale or dirt that may be caught in the BD2 Re tighten th...

Отзывы: