background image

 

172-65451MA-04  (JH5RL-X)    3  Jul  2018

 

12

 

Instructions for Plug/Holder Disassembly and Reassembly

 

The seal on the threaded plugs/holders found on TLV products is formed by a flat 
metal gasket. There are various installation orientations for the gaskets, such as 
horizontal, diagonal and downward, and the gasket may be pinched in the thread 
recesses during assembly. 

Instructions for Disassembly and Reassembly 

1.  Remove the plug/holder using a tool of the specified size (distance across flats). 

2.  The gasket should not be reused. Be sure to replace it with a new gasket. 

3.  Clean the gasket surfaces of the plug/holder and the product body using a rag and/or 

cleaning agents, then check to make 
sure the surfaces are not scratched or 
deformed. 

4.  Coat both the gasket surface of the 

plug/holder and the threads of the 
plug/holder with anti-seize, then 
press the gasket onto the center of 
the gasket surface of the plug/holder, 
making sure the anti-seize affixes the 
gasket tightly to the plug/holder. 
Check to make sure the gasket is 
not caught in the recesses of the 
threads. 

5.  Hold the plug/holder upside down to 

make sure that the anti-seize makes 
the gasket stick to the plug/holder 
even when the plug/holder is held 
upside down. 

6.  Screw the plug/holder by hand into 

the product body while making sure 
that the gasket remains tightly 
affixed to the center of the gasket 
surface of the plug/holder. Make sure the entire gasket is making contact with 
the gasket surface of the product body. It is important at this point to make sure 
the gasket is not pinched in the thread recesses of the plug/holder. 

7.  Tighten the plug/holder to the proper torque. 

8.  Next, begin the supply of steam and check to make sure there is no leakage 

from the part just tightened. If there is leakage, immediately close the inlet valve 
and, if there is a bypass valve, take the necessary steps to release any residual 
pressure. After the surface of the product cools to room temperature, repeat the 
procedure beginning from step 1. 

 

Gasket

Do not pinch gasket in

threaded recesses

Coat with
anti-seize

Gasket Surface

3)

4)

5)

6)

Содержание JH5RL-X

Страница 1: ...172 65451MA 04 JH5RL X 3 July 2018 Free Float Steam Trap with X element JH5RL X Copyright 2018 by TLV CO LTD All rights reserved ...

Страница 2: ... changes in temperature and responds with great accuracy As a result air and the large quantities of condensate created immediately after the start up of operation are quickly discharged thereby greatly reducing start up time and also proving useful in valve operation bypass blowdown labor saving The X element is also sensitive to hot air during operation responding quickly and thus preventing the...

Страница 3: ...eat of death or serious injury WARNING Indicates that there is a potential threat of death or serious injury CAUTION Indicates that there is a possibility of injury or equipment product damage WARNING NEVER apply direct heat to the float The float may explode due to increased internal pressure causing accidents leading to serious injury or damage to property and equipment CAUTION Install properly ...

Страница 4: ...recommended components when repairing the product and NEVER attempt to modify the product in any way Failure to observe these precautions may result in damage to the product and burns or other injury due to malfunction or the discharge of fluids Use only under conditions in which no freeze up will occur Freezing may damage the product leading to fluid discharge which may cause burns or other injur...

Страница 5: ...ack pressure has a check valve TLV CK been installed 5 Is the inlet pipe as short as possible with as few bends as possible and installed so the liquid will flow naturally down into the trap 6 Has the piping work been done correctly as shown in the figures below Requirement Correct Incorrect Install catchpot with the proper diameter Diameter is too small Make sure the flow of condensate is not obs...

Страница 6: ...ng condensate level causes the float to rise due to buoyancy opening the orifice B and allowing condensate to be discharged 3 Hot Air Discharge Should hot air flow into the trap during normal operation the temperature of the X element drops causing it to momentarily contract and open the air vent valve A which allows for the rapid discharge of the air After the air is discharged and steam contacts...

Страница 7: ...te for detailed specifications Model Maximum Allowable Temperature TMA Maximum Allowable Pressure Nominal Diameter Maximum Differential Pressure Production Lot No Valve No Maximum Operating Temperature Maximum allowable pressure PMA and maximum allowable temperature TMA are PRESSURE SHELL DESIGN CONDITIONS NOT OPERATING CONDITIONS Valve No is displayed for products with options This item is omitte...

Страница 8: ...discharge of fluids CAUTION Installation inspection maintenance repairs disassembly adjustment and valve opening closing should be carried out only by trained maintenance personnel 1 Before installation be sure to remove all protective seals 2 Before installing the product open the inlet valve and blow out the piping to remove any piping scraps dirt and oil Close the inlet valve after blowdown 3 I...

Страница 9: ...steam and the sound of flow can be heard If there is very little condensate there is almost no sound of flow Blocked Discharge Impossible No condensate is discharged The trap is quiet and makes no noise and the surface temperature of the trap is low Blowing Live steam continually flows from the outlet and there is a continuous metallic sound Steam Leakage Live steam is discharged through the trap ...

Страница 10: ...he proper torque Drain Plug Gasket Remove the gasket and clean sealing surfaces Replace with a new gasket coat surfaces with anti seize Detaching Reattaching the Cover Part During Disassembly During Reassembly Cover Nut Remove with a socket wrench Consult the table of tightening torques and tighten to the proper torque Cover Remove by lifting up and off Make sure there are no pieces of the old gas...

Страница 11: ...fice Plug Gasket Remove the gasket and clean sealing surfaces Replace with a new gasket coat surfaces with anti seize Orifice Remove with a socket wrench Consult the table of tightening torques and tighten to the proper torque Orifice Gasket Remove the gasket and clean sealing surfaces Replace with a new gasket coat surfaces with anti seize Table of Tightening Torques Part Name Torque Distance Acr...

Страница 12: ... Jul 2018 11 Exploded View X element Guide Air Vent Valve Seat Cover Nut Cover Screen Float Cover Bolt Body Orifice Gasket Orifice Orifice Plug Gasket Orifice Plug Connector Connector Gasket X element Spring Clip Cover Gasket ...

Страница 13: ... affixes the gasket tightly to the plug holder Check to make sure the gasket is not caught in the recesses of the threads 5 Hold the plug holder upside down to make sure that the anti seize makes the gasket stick to the plug holder even when the plug holder is held upside down 6 Screw the plug holder by hand into the product body while making sure that the gasket remains tightly affixed to the cen...

Страница 14: ...maximum specified pressure or whether there is insufficient pressure differential between the trap inlet and outlet Compare specifications and actual operating conditions Steam is discharged or leaks from the outlet blowing steam leakage Build up on the seating surface of the orifice or rust and scale build up beneath the float Clean parts Scratches on the orifice Replace with a new orifice The fl...

Страница 15: ...improper installation use handling etc by other than TLV CO LTD authorized service representatives 2 Malfunctions due to dirt scale rust etc 3 Malfunctions due to improper disassembly and reassembly or inadequate inspection and maintenance by other than TLV CO LTD authorized service representatives 4 Malfunctions due to disasters or forces of nature 5 Accidents or malfunctions due to any other cau...

Страница 16: ...crewdriver into the slot on the top of the needle valve and Open Valve slowly turn counterclockwise Do not continue turning the needle valve past the point at which the snap ring contacts the bottom of the gland case See the table below to determine the amount of steam discharge Close Valve slowly turn clockwise Do not continue turning the needle valve past the point at which it stops 3 If steam s...

Страница 17: ... MPa Discharge Capacity lb h Differential Pressure psi Discharge Capacity kg h Differential Pressure kg cm 2 More than 1 5 turns 1 Turn Turn Turn Turn Number of turns from full closed position More than 1 5 turns 1 Turn Turn Turn Turn Number of turns from full closed position ...

Отзывы: