172-654741MA-01 (CV-COS-20/CV-COS-20D) 7 Oct 2021
10
4. Removing any protective caps and seals
Before installation, be sure to remove all protective seals and caps. (Found in
three locations, on the product inlet and outlets.)
CV-COS-20
CV-COS-20D
5. Installation angle
Install the product so that the arrow mark on the valve body points horizontally in
the direction of steam flow, and it should be installed horizontally in the piping
with the actuator at the top. Allowable inclination is 10 degrees in the fore-aft
direction and 15 degrees in the plane perpendicular to the steam flow line.
CV-COS-20
CV-COS-20D
6. Piping support
Install the product, paying attention to avoid excessive load, bending and
vibration. Support the inlet and outlet pipes securely.
CV-COS-20
CV-COS-20D
①
②
③
①
②
③