30
Afbeelding
T-568B
7.3.2.1
Connection of kpBus
When using shielded cable, one end of the cable’s metal sheath must be attached
to the earth
ground connection
⏚
in the system cabinet.
NOTE
the Polyx is always the starting point of a kpBus. Add an EOL jumper to the end
of the kpBus, see
7.3.3
Connection via an adapter board
If no direct UTP connection between the network controller and the Orion is possible, an adapter
board can be used.
Possible reasons for the use of an adapter board include:
•
The Orion and the network controller are mounted in different buildings, so the connection
cable exits the building
•
The connection cable is not
–
or is not guaranteed to be
–
a (
≥Cat5e
) UTP cable (e.g. if an
existing connection cable is being reused)
•
Surge protection is required
The adapter board along with the network controller are connected using standard UTP
≥Cat5e
cable (plug-in connection).
For more information, please refer to the adapter board manual.
7.3.3.1
Wiring requirements
Recommended cable for communication bus between network controller and Orion(s):
Polyx
PRT1
–
2
Orion
(I)
A B C
S
Nr.
Description
Wire color
1 RxA
White/orange
B
2 RxB
Orange
A
3 TxZ
White/green
B
4 +12Vdc
Blue
-
5 Orbit sense
White/blue
-
6 TxY
Green
A
7 GND
White/brown
C
8 GND
Brown
C
Cable
Communication
protocol
Total kpBus distance (metres)
UTP ≥Cat5e
RS485
600
Twisted pairs of 24AWG (at least)
copper conductors, shielded
PRT2
A B C S
I
Illustration
of kpBus
connection
X
Содержание KEYPROCESSOR Orion
Страница 1: ...1 Pluto Orion Doc no 01052018 Modular controller line Installation instructions ...
Страница 4: ...4 ...
Страница 57: ...57 14 Technical drawings 14 1 72000310 Pluto Orion setup with network connection and power supply ...
Страница 58: ...58 14 2 72000206 Pluto Orion with Sirius RS485 and IO ...
Страница 59: ...59 14 3 72000202 Pluto Orion with Sirius clock data Wiegand and I O ...
Страница 60: ...60 14 4 72000207 Pluto Orion with IO Sirius Clock data Wiegand and Orbits ...
Страница 61: ...61 14 5 72000304 Pluto with power supply and USB RS232 converter ...
Страница 62: ...62 14 6 72000203 Pluto Orion with kpBus ...
Страница 63: ...63 14 7 72000204 Orion with kpSensor bus ...
Страница 64: ...64 14 8 72000602 Pluto Orion stacked with 8x RS485 Sirius i readers ...
Страница 65: ...65 14 9 72000602 Pluto Orion with clock data or Wiegand readers ...
Страница 66: ...66 14 10 72000602 Pluto Orion with RS485 readers kpBus combi ...
Страница 67: ...67 14 11 72000504 Polyx with kpBus ...