2.4 Electrical Hazards
When installing this equipment always follow these safety rules:
•
Never touch exposed electrical connections on this equipment while the power is ON.
•
Do not attempt to operate or service electrical equipment if standing water is present.
•
When working on the equipment always wear required protective clothing.
•
Never open the equipment while the power is ON.
This equipment contains electrostatic sensitive devices that can be damaged by an electrostatic discharge.
•
Protect the equipment from electrostatic discharge.
•
Before touching any component of the cabinet, bring your body to the same potential
as the cabinet by touching a conductive earthed part of the cabinet.
•
Electronic modules or components must not be brought in contact with highly
insulating materials such as plastic sheets or synthetic fibre clothing. They must be
laid down on conductive surfaces.
When installing or de-installing the equipment, follow the additional safety instructions in in Chapter 5
Installation Safety on page 16 and Chapter 7 Maintenance Safety on page 27.
2.5 Transport and Storage
Transport
•
Use extreme care when moving heavy products. Verify that the moving equipment is rated to handle the
weight. When loading or unloading, ensure that the products are carefully balanced and secured using a
safety strap.
•
No more than 6 packaged products may be placed on one transport pallet.
Storage and reforming
•
If the equipment is stored before installation, it must be protected from the weather and kept free of
condensation and dust.
•
Keep the equipment in the original packing it was shipped in, until it is going to be installed.
•
If the equipment is stored for longer than 6 months before installation, it must be temporarily energized.
This reforming procedure should be done at least once every 12 months, in an environment free of
condensation and dust.
1.
Unpack the equipment.
2.
Follow the installation procedure in Wall-mounting Instructions on page 20.
3.
Follow the connection procedure in Connecting Instructions on page 22.
The CEDD
®
power output must be short-circuited.
4.
Switch the equipment on and wait for at least 1 hour.
5.
Switch the equipment off.
6.
Wait for 15 minutes.
7.
Follow the disconnecting procedure in Replacing a CEDD
8.
Repack the equipment in its original packaging.
10
Installation and Maintenance Manual - CEDD
®
HPS Basestation
©
TKH Airport Solutions 2022. All rights reserved. All specifications subject to change without notice.