background image

reading of  -.02 to -.03” W.C..  

IMPORTANT:

If a minimum of -.02” W.C. cannot be obtained by adjusting the barometric 

damper closed (more draft),  the SS1 draft control on the vent hood should be pushed out (more draft) and the barometric 
damper readjusted to reach -.02 to -.03” W.C.. 

6. Perform a smoke test and make any adjustments to the burner air shutter, SS1 draft control on the vent hood or the barometric 

draft control to arrive at a trace of smoke (between 0 and 1) at a minimum over fire draft of -.02” W.C..

7. Perform a CO

2

test at the same location as the smoke test. Reduce the CO

2

1% to 2% by opening the burner air shutter. 

Recheck over fire draft and increase venter draft or adjust barometric damper closed (more draft) if necessary to maintain a 
minimum of -.02” W.C..  

Do not allow heating system to run at less than a -.02” W.C. over fire draft or at a CO

2

level that is less than a 1% reduction from

the value measured at a trace of smoke and a -.02” W.C. over fire draft. If these parameters are unobtainable, contact Tjernlund at
1-800-255-4208 for Technical Assistance. 

8.  Remove the call for heat from the heating system.  

NOTE:

The SS1 will run in post-purge mode which is factory set at 2

minutes and adjustable up to 16 minutes.  Allow the system to cool down to ambient room temperature.

9.  Restart the heating system.

10. At 5 minutes into the restart, read and record the inlet temperature  ________F.  If  this temperature is above 250

0

F, continue to 

step 11. If this temperature is below 250

0

F,  use an approved insulated pipe / vent connector.  Verify that the over fire draft and 

CO

2

have not changed,  If they have, redo the adjustment steps.  With insulated pipe / vent connector, redo the 5 minute tem-

perature test and record the new value here ________F.  If insulated pipe / vent connector did not increase the inlet tempera-
ture above 250

0

F. within 5 minutes of the heating system call for heat, call 800-255-4208 for technical support.

11. Lock down the burner primary air adjustment, the barometric adjustment knob and the SS1 draft adjustment with four lock nuts

on adjustment cone brackets, (See Diagram P).  Verify the over fire draft and CO

2

readings have not changed from the earlier values.

DRAFT ADJUSTMENT PROCEDURE FOR GAS EQUIPMENT

DRAF

The SideShot Vent System will properly vent a wide range of BTU/hr. input capacities.  To compensate for different burner capaci-
ties, vent connector lengths and wind conditions it features a draft adjustment located on the outside of the Vent Hood.  In general,
positioning the draft adjustment 

inward

will cause the SideShot to operate at lowest capacity.  Positioning the draft adjustment

outward

will cause the SideShot to operate at highest capacity.

IMPORTANT:

The following paragraph describes the initial draft adjustment.  It may be necessary to make a slight readjustment to compensate
for various conditions: wind, vent connector resistance, negative building pressure and multiple appliances.

ASHRAE lists the average design factor for wind loads in North America at 15 MPH.  Refer to the Draft Adjustment Chart on Page
17.  We recommend that the 25 MPH category be used to allow for excursions beyond the 15 MPH average.  It is not recom-
mended for the SideShot to be terminated on a wall that faces the direction of the prevailing winds.  Backdrafts by severe winds
can interrupt heating equipment operation.  If the SideShot is terminated in a direction prone to higher winds, or if higher winds are
common in your geographic area, use the 40 MPH category to determine the proper draft adjustment setting.  If the draft adjust-
ment is set at the 25 MPH category and sustained winds exceeding 25 MPH are present, the Fan Proving Switch will disrupt the
burner until the wind load drops below 25 MPH.  Wind loads are based on straight line winds directed against the Vent Hood.

IMPORTANT:

Before proceeding, close all windows, doors and fireplace dampers.  Turn on all appliances in the structure that exhaust indoor air
such as clothes dryer, exhaust fans, range hoods, bathroom and whole house exhaust fans.  Failure to perform the draft adjust-
ment procedure may cause a poor vent system installation possibly resulting in fire, carbon monoxide poisoning, explosion, per-
sonal injury or property damage.

DRAFT ADJUSTMENT PROCEDURE

1.  Set the draft adjustment on SS1 Vent Hood to the appropriate setting based on the above instructions and the Draft Adjustment 

Chart.  Adjustment is accomplished by loosening both nuts on each side of the Vent Hood and centering 

both

indicators to the 

desired setting.  Tighten the four nuts to secure the draft adjustment at desired setting.

2.  Place the heating system into operation. 

NOTE:

there will be a slight pause between venter operation and burner operation. A 

Venter pre-purge of up to a minute may also be selected.  See “Pre / Post-Purge Settings” on page 5.   If  installation uses a 
barometric draft control adjust it to the minimum or least draft setting. Allow heater to operate for 5 minutes.

3. 

PREFERRED METHOD:

MUST HAVE DRAFT GAUGE AVAILABLE

Sample draft one foot after draft hood, diverter or barometric draft control using a draft gauge. If the draft reading is in excess of
-0.05” W.C. adjust SS1 Vent Hood cone in (less draft) or adjust barometric for (less draft) so that a draft reading of -0.02” to 
-0.05” W.C. is obtained.  Never adjust draft to a setting of less than -0.02” W.C. If the vent system is terminated on a wall 
subject to prevailing winds a -0.05” W.C. draft setting is recommended.

4. If a draft gauge is not available test for spillage at the draft hood, diverter or barometric draft control using the flame from a 

match, lighter or candle and determine the following:

A. The flame or smoke is being drawn into the draft hood, diverter or barometric draft control.

B. The main burner is burning properly, i.e. no floating, lifting or flash back.

18

Содержание SideShot SS1

Страница 1: ...CTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION ADJUST MENT SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE ELECTRI CAL SHOCK CARBON MONOXIDE POISONING EXPLOSION OR PERSONAL INJURY OR PROPERTY DAMAGE DO NOT DESTROY PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE MODEL SS1 INSTALLATION INSTR...

Страница 2: ...d Terminus 25 SideShot is a registered trademark of Tjernlund Products Inc for their Models SS1 SS2 Vent Systems DESCRIPTION The SS1 is a mechanical vent system designed and listed for use with natural draft oil or gas heating equipment It is factory assembled and wired The SS1 automatically vents the flue gases from heating equipment to the outdoors By combining outside air with high tech insulat...

Страница 3: ...led where flue gas temperatures exceed 301oC 575oF at its inlet Flue gas temperature verification A On oil fuel verify flue gas temperature at SS1C inlet is at or above 250oF 121oC after 5 minutes of operation during setup See Oil Draft Adjustment Procedure on page 17 step 10 AND B Measure temperature of flue gases at the inlet to the SideShot at time of installation Temperature should be measured...

Страница 4: ...SLY USED APPLIANCE Perform prior to SideShot installation The following procedure is intended as a guide to aid in determining that an appliance is properly installed and is in safe condition for continuing use This procedure is based on central furnace and boiler installations and it should be recognized that general ized procedures cannot anticipate all situations Accordingly in some cases devia...

Страница 5: ...en remove call for heat 4 LED STATUS LIGHTS See LED Status Fault Indicator Section for details LED 1 AMBER LED 2 GREEN LED 3 GREEN LED 4 RED LED 5 RED DRY 24 V 115 V J1 J2 CALL JUMPER Used when the call signal is used as the proven return signal to the appliance See wiring section for details APPLIANCE INTERLOCK TERMINAL BLOCK A B 1 4 A B Dry Contact call 3 mA 5VDC SEE WARNING 1 1 24 or 115 VAC in...

Страница 6: ... cycle nozzle drip odor A longer post purge may be necessary for longer vent runs or high heat retention refractory lined combustion chambers A shorter post purge may be desired for gas installations 5 Pre Purge Post Purge Prover Status Check Activated DIP SWITCH NUMBERING 1 ON ON ON PRE PURGE SETTINGS ON POST PURGE SETTINGS ON P1 P2 FAN PROVER SAFETY CIRCUIT OPEN UPON APPLIANCE CALL The Prover St...

Страница 7: ... below 4 feet horizontally from or 1 foot above any door window or gravity air inlet into any building The bottom of the vent terminal shall be located at least 12 inches above grade The exit terminal shall be so arranged that the flue gases are not directed so as to jeopardize people overheat combustible structures or enter buildings Not to be less than 10 feet from an adjacent building The SideS...

Страница 8: ...holes previously created in Step 2 4 Drill the four corner holes noted on the template through the building exterior Remove the template and mark lines from the outside edge of the holes drilled forming a rectangle 5 Using reciprocating saw and appropriate blade cut a rectangular opening through the rim joist wall board siding etc on the lines marked in step 4 The rectangular opening should be no ...

Страница 9: ...learance for the SideShot motor 1 Attach Template B Page 24 to the floor joist that is to be notched aligning the sight line noted on the template with the end or the outside casing of the vent hood 2 Cut out notch on line shown on the template 8 DIAGRAM G DIAGRAM F DIAGRAM D DIAGRAM E NOTE For mounting on vinyl or lap siding a wood frame with 1 x 1 1 2 on the sides and top and 1 x 2 material on b...

Страница 10: ...m the bottom upward over the the slip joint guides as far as possible by hand A hammer may be used to tap the slip joint drivers to their final position Start the slip joint drivers on the slip joint guides with the embossed end facing down Do not force slip joint drivers past embossing INSTALLATION OF WALL SUPPORT BRACKET 1 To prevent damage to the SideShot temporarily support the bottom of the p...

Страница 11: ...uns of over 15 linear feet should use an approved insulated vent connector to prevent problems related to sulfur condensation It is not necessary to maintain a 1 4 rise per every foot of horizontal when Side Wall Venting The SideShot Vent System is shipped from the factory with the plug connected to the rear and the vent pipe inlet collar connected to the bottom If using the bottom inlet skip to t...

Страница 12: ...the inlet collar Take care not to crimp the tubing 8 Install the plug removed in step 1 over the bottom inlet port tightening securely VENT PIPE CLAMP ASSEMBLY 1 Attach the three vent pipe clamps to the inlet collar See Diagram N NOTE The following diagrams show the use of the rear inlet The same steps will apply if using the bottom inlet 2 Bend each vent pipe clamp so it conforms to the outside d...

Страница 13: ...o the burner motor Choose the interlock method that best fits your application The steps listed under each diagram are intended as a supplement to the diagram Wiring colors or designations may vary by manufacturer If you are unable to wire the SS1 as outlined in these instructions call Tjernlund s Customer Service Department toll free at 1 800 255 4208 for assistance IMPORTANT To reset faults veri...

Страница 14: ...1 electrical box 7 Make sure RED voltage jumper on UC1 is on 115V SIDESHOT WITH INTEGRAL UC1 UNIVERSAL CONTROL CONNECTED TO A HONEYWELL R7184 SERIES OR EQUIVALENT PRIMARY CONTROL WITH A LINE VOLTAGE THERMOSTAT OR AQUASTAT Burner Alarm Cad Cell A Interrupted Intermittant Motor A IGNITION TRANS BURNER MOTOR R Oil Valve Limit R7184 L1 T T L2 OIL VALVE 115 VAC 60 Hz SUPPLY Limit 24V DRY 115V XL UNIVER...

Страница 15: ...115V NOTE If burner primary control goes out on lockout the SideShot will continue to run as long as a call for heat is present SIDESHOT WITH INTEGRAL UC1 UNIVERSAL CONTROL CONNECTED WITH A CARLIN 40200 42230 48245 50200 60200 SERIES OR EQUIV AND A LINE VOLTAGE THERMOSTAT OR AQUASTAT Alarm A Violet 0 3 A AC OIL VALVE R A Blue Orange F F White T Black Red White T 115 VAC BURNER MOTOR IGNITION TRANS...

Страница 16: ...l on UC1 and neutrals to White or N 6 Connect 115 VAC supply voltage to L N terminals on UC1 Installer must supply overload and disconnect protection 7 Crimp ground wire to grounding spade in SS1 electrical box 8 Make sure RED voltage jumper on UC1 is on 115V SIDESHOT WITH INTEGRAL UC1 UNIVERSAL CONTROL CONNECTED WITH A SINGLE ZONE 24 VAC THERMOSTAT XN R UNIVERSAL CONTROLLER THERMOSTAT G G INTERNA...

Страница 17: ... grounding spade in SS1 electrical box 6 Make sure RED voltage jumper on UC1 is on 24V SIDESHOT WITH INTEGRAL UC1 UNIVERSAL CONTROL CONNECTED WITH A 24 OR 115 VAC STANDING PILOT 115V 24V DRY OF FURNACE BOILER INTERNAL CONTROLS 24V OR 115V GAS VALVE HOT COM B2 COM TR Aquastat T stat TH HOT B1 XL UNIVERSAL CONTROLLER XN J1 J2 D N 9183046 1 24 OR 115 VAC LEGEND CALL JUMPER 115 VAC 50 60 Hz SUPPLY 115...

Страница 18: ...hat exhaust indoor air such as clothes dryer exhaust fans range hoods bathroom and whole house exhaust fans Failure to perform the draft adjust ment procedure may cause a poor vent system installation possibly resulting in fire carbon monoxide poisoning explosion per sonal injury or property damage 1 Set the draft adjustment on SS1 Vent Hood to the appropriate setting based on the above instructio...

Страница 19: ... compensate for various conditions wind vent connector resistance negative building pressure and multiple appliances ASHRAE lists the average design factor for wind loads in North America at 15 MPH Refer to the Draft Adjustment Chart on Page 17 We recommend that the 25 MPH category be used to allow for excursions beyond the 15 MPH average It is not recom mended for the SideShot to be terminated on...

Страница 20: ...riod set after the burner stops firing See Pre Post Purge Settings on page 5 7 Return all windows doors and exhaust fans to their original conditions of use TROUBLESHOOTING OIL ODORS Many problems can be eliminated quite easily by having the equipment properly set up by a professional oil heat service contrac tor The sophistication of today s heating equipment and instrumentation needed for effici...

Страница 21: ...assistance IMPORTANT To reset faults verify fault by checking the LEDs and then remove call for heat LED STATUS FAULT INDICATORS LED INDICATOR LIGHTS LED 1 Amber Appliance call for heat LED 2 Green Safety circuit through P1 P2 SS1 Limit Fan Prover is verified Open upon start up Burner circuit is energized with contact closure from terminal 3 to 4 Also verifies SS1 prover limit are closed during ru...

Страница 22: ...C1 control LED 2 Green should light No LED 2 Green does not light Replace UC1 circuit board part number 950 8801 Yes LED 2 Green lights up Remove supply power to UC1 Remove Jumper from P1 P2 The SS1 high limit is open the fan proving switch is not closing or wiring connections are incorrect broken Disrupt call for heat Push reset button on SS1 high limit inside electrical box NOTE Insufficient pos...

Страница 23: ... allen wrench 2 Twist wheel to loosen and pull off of motor shaft Do not pull too hard wheel may bend Wheels fused to shaft may require penetrating oil and or a wheel puller to facilitate removal 3 Slide new wheel on to flat of shaft and firmly tighten set screw MOTOR OILING The SideShot motor is permanently lubricated and requires no oiling HOW TO OBTAIN SERVICE ASSISTANCE 1 If you have any quest...

Страница 24: ...uct that has been wired incorrectly Product that has been damaged by a malfunctioning or mistuned burner Any freight charges related to the return of the defective part Any labor charges related to evaluating and replacing the defective part REPLACEMENT PARTS Component Part Number Motor w Wheel 950 0625 Proving Switch 950 0650 Wheel 950 0635 High Limit Switch 950 0640 Universal Control Circuit Boa...

Страница 25: ...24 ...

Страница 26: ...BACKSIDE OF TEMPLATE B ...

Страница 27: ...25 ...

Отзывы: