ELECTRICAL WIRING
All wiring from the SS1 to the appliance must be appropriate Class 1 wiring as follows: installed in rigid metal conduit, intermediate
metal conduit, rigid non-metallic conduit, electrical metallic tubing, Type MI Cable, Type MC Cable, or be otherwise suitably protected
from physical damage.
SS1 SEQUENCE OF OPERATION WITH INTEGRAL UC1 UNIVERSAL CONTROL:
Control signal from thermostat, aquastat, primary control or gas valve is intercepted and routed to terminal “1” on UC1 terminal
strip. When terminal “1” is energized with either 24 VAC or 120 VAC, the SS1 motor is energized. After draft is established, the
Fan Proving Switch closes within 5 to 10 seconds energizing terminal “4”, which completes the circuit allowing burner to fire.
NOTE:
If a venter pre-purge is selected, the burner will not fire until the pre-purge time is finished. The SS1 will continue to run
after the burner has finished firing for the set post-purge time cycle. The SS1 is set for a 2 minute post-purge time period from the
factory. See “Pre / Post-Purge Settings” on page 5 for details.
The "1" input terminal on the SideShot can accept either a 24 VAC or 120 VAC control signal. IMPORTANT:
The RED
jumper must be positioned based on appliance interlock voltage. For most furnace applications it may be easier to interlock with
the 24 VAC thermostat circuit. For most boiler applications it may be easiest to interlock with the 120 VAC aquastat or primary
control circuit to the burner motor. Choose the interlock method that best fits your application.
The steps listed under each diagram are intended as a supplement to the diagram. Wiring colors or designations may vary by
manufacturer. If you are unable to wire the SS1 as outlined in these instructions, call Tjernlund’s Customer Service Department
toll free at 1-800-255-4208 for assistance.
IMPORTANT:
To reset faults, verify fault by checking the LEDs and then remove call for heat.
SS1 WITH INTEGRAL UC1 UNIVERSAL CONTROL
(THE SS1 MOTOR, LIMIT & PROVER ARE ALL FACTORY PREWIRED)
12
IMPORTANT:
RED JUMPER POSITION MUST BE THE SAME
AS APPLIANCE INTERLOCK VOLTAGE.
CALL
RELAY
INTERLOCK
COMMON
NEUTRAL
PRODUCTS,
INC.
SS1 MOTOR
1 H.P. MAX @ 115 VAC
SUPPLY
115 VAC
50/60 Hz
R
TJERNLUND
9183006
NO
MTR
M
MOTOR
RELAY
N
COM
NO
115 VAC
24 VAC
1303960-1
DO NOT SUPPLY VOLTAGE
TO "A" OR "B".
DO NOT SUPPLY POWER!
5 VDC BOARD-GENERATED POWER
HOT
24 VAC
USER-PROVIDED
CALL SWITCH
LINE
OR
"DRY"
OR
115V
J2
COM
24V
DRY
LEGEND:
115 VAC
5
POST-PURGE SETTINGS
FOR TJERNLUND
TO P1, P2, C, GND
AUXILIARY
OR F. DOING SO
WILL DAMAGE THE
CONNECT POWER
OPEN PROVER OPTION
(9)
(3 - 8)
9
7
8
6
CONTROL.
DEVICES. DO NOT
F
GND
ON
LED1
PRE-PURGE SETTINGS
LED5 LED4
LED2
LED3
(1 - 2)
2
4
3
1
C
P1
P2
J1
XL
XN
115 OR 24 VAC FROM CALL JUMPER
OR USER-PROVIDED VOLTAGE
FROM TERMINAL 3 TO 4 WITH CALL
JUMPER REMOVED
K2
K1
APPROVED
MAC1E OR MAC4E
JUMPER
RED
RED
GREEN
GREEN
AMBER
SS1 PROVER
SS1 LIMIT
WARNING:
Disconnect power supply from the SS1 and heating equipment when making wiring connections and servicing the
SS1. Failure to do so may result in personal injury and/or equipment damage. LED #5 (RED) should be off with
power removed.