SEQUENCE OF OPERATION FOR HS-3C ON A SINGLE APPLIANCE

The following sequence of operation gives guidance as to how the Power Venter should operate with the appliance.

1. The call for heat will be routed through the Motor Relay and to one side of the Fan Proving Switch. The Power Venter motor is 

energized.

2. When the Power Venter has achieved full RPM and maximum draft has been established, the Fan Proving Switch will close  

allowing the 24V signal to energize the Isolation Relay coil.

3. When the Isolation Relay contacts close, the 24V signal will then be allowed to reach the gas valve.

DRAFT ADJUSTMENT

DRAFT ADJUSTMENT FOR GAS APPLIANCES EQUIPPED WITH A DRAFT HOOD OR DRAFT DIVERTER

1. With the appliance(s) and Power Venter operating for at least 15 minutes, hold a taper, cigarette or other smoke producing device 

at the draft hood or draft diverter.

2. Determine that the smoke is being drawn into the vent system.

3. If the draft appears to be excessive, the damper on the Power Venter may be adjusted to reduce the Power Venter’s performance 

as long as the smoke is still being drawn into the draft hood after damper adjustment.

DRAFT ADJUSTMENT FOR GAS APPLIANCES EQUIPPED WITH A BAROMETRIC DRAFT CONTROL

1. With the appliance(s) and Power Venter operating for at least 15 minutes, insert a draft gauge into the vent pipe between the 

barometric draft control and the appliance flue outlet.

2. Make necessary draft adjustments with the barometric draft control, appliance burner air intake and the damper located on the 

outlet of the Power Venter until the appliance manufacturer’s recommended draft is present.

SAFETY INTERLOCK TEST

1. Adjust the appliance thermostat(s) or aquastat(s) to call for heat.

2. Determine that the Power Venter operates before the gas valve becomes energized.

3. With the appliance(s) and Power Venter operating, disrupt power to the Power Venter and determine that the appliance gas valve 

shuts off.

DO NOT OPERATE AN APPLIANCE THAT DOES NOT SHUT OFF WITH THE VENTER DISABLED.

MAINTENANCE

1. Oil every six months with 2 drops of S.A.E. #20. The oil ports are located at both ends of the motor.

2. A vent pipe inspection must be performed annually.  The inspection should include checking all vent pipe and connections for 

blockage and leaks. A safety interlock test should also be performed.

HOW TO OBTAIN SERVICE ASSISTANCE

1.

If you have any questions about your Power Venter or if it requires adjustment, repair or routine maintenance, we suggest that
you contact your installer, contractor or service agency. 

2.

If you require technical information contact Tjernlund Products, Inc. at 1-800-255-4208.

When contacting Tjernlund Products, Inc., please have the following information available:

1.

Model number of the Power Venter 

2.

Name and address of installer and service agency

3.

Date of original installation and dates any service work was performed

4.

Details of the problem

Содержание HS-3C CANADIAN 8504002 REV 2 0997

Страница 1: ... THIS UNIT READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION ADJUST MENT SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE ELECTRI CAL SHOCK CARBON MONOXIDE POISONING EXPLOSION PERSONAL INJURY OR PROPERTY DAMAGE DO NOT DESTROY PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE ON JOB SITE FOR FUTURE R...

Страница 2: ...ction should occur SPECIFICATIONS CAPACITY The installer must verify that the Power Venter is sized properly using the capacity table to the right The installer may reduce the vent pipe diameter to the size shown in the selection table immediately after the draft hood draft diverter or barometric draft control The vent pipe length shown includes all equivalent vent pipe before and after the Power ...

Страница 3: ...diverter or barometric draft control 5 The Power Venter shall not be installed where the flue gas temperature exceeds 285oC 550o F at the Power Venter inlet Flue gas temperature verification A Consult appliance manufacturer for flue gas temperature after dilution by the draft hood draft diverter or barometric draft control B Measure flue gas temperature at the Power Venter inlet after installation...

Страница 4: ... A venting system shall not direct flue gases towards brickwork siding or other construction in such a manner that may cause damage from heat or condensate from the flue gases A vent system shall not direct flue gases so as to jeopardize people overheat combustible structures or enter buildings A venting system shall not terminate within 1 8 m 6ft of the following A window door or mechanical air s...

Страница 5: ...appropri ate type of vent pipe to the inlet of the Power Venter The vent pipe chosen must be in compliance with local codes The Power Venter inlet and outlet are designed to accept single wall vent pipe If using vent pipe other than single wall the installer must supply adapters to connect to the Power Venter While it is recommended that the Power Venter be mounted at the point of termination it i...

Страница 6: ...at is on the exterior of the housing DO NOT trim the sensing tube portion that will be mounted in the interior of the housing No attempts should be made to substitute the specified materials See Fan Proving Switch installation diagram WIRING All wiring from the Power Venter to the appliance must be in compliance with the local codes or in their absence The Canadian Electrical Code CSA Std C22 1 Al...

Страница 7: ...he installer needs to complete 3 steps to wire the Power Venter as noted below 1 Route the metal conduit from the electrical box to the Power Venter motor and connect the Black White and Ground wires to the motor 2 Connect the Red Blue and Orange wires in the electrical box to the appliance 3 Supply 115 VAC to the input wires in the electrical box NOTE The HS 3C as viewed from the opposite end of ...

Страница 8: ...HS 3C Power Venter is interlocked to 24V controlled appliances Variations of these diagrams are acceptable as long as the Fan Proving Switch isolation circuit is wired to disable the gas valve if a venting mal function should occur 7 HS 3C CONNECTED TO APPLIANCE WITH SPARK IGNITION HS 3C CONNECTED TO A BOILER ...

Страница 9: ...ometric draft control and the appliance flue outlet 2 Make necessary draft adjustments with the barometric draft control appliance burner air intake and the damper located on the outlet of the Power Venter until the appliance manufacturer s recommended draft is present SAFETY INTERLOCK TEST 1 Adjust the appliance thermostat s or aquastat s to call for heat 2 Determine that the Power Venter operate...

Страница 10: ...Housing WHAT IS NOT COVERED Product installed contrary to our installation instructions Product that has been altered neglected or misused Product that has been wired incorrectly Product that has been damaged by a malfunctioning or mistuned burner Any freight charges related to the return of the defective part Any labor charges related to evaluating and replacing the defective part REPLACEMENT PAR...

Отзывы: