CAUTIONS

1. Failure to install, maintain and/or operate the MAC-3 in accordance with manufacturer’s instructions may result in conditions that 

can produce bodily injury and property damage.

2. The safety interlock and system operation performance checks must be performed on each appliance interlocked with the 

MAC-3 in accordance with the Power Venter, Draft Inducer, IN-FORCER or Damper installation instructions.

ELECTRICAL

All wiring from the MAC-3 to the appliance must be appropriate Class 1 wiring as follows: installed in rigid metal conduit, intermediate conduit,
rigid non-metallic conduit, electrical metallic tubing, Type MI Cable, Type MC Cable or be otherwise suitably protected from physical damage.  

The disconnect means and circuit protection are to be provided by the installer of this device.

SEQUENCE OF OPERATION OF MAC-3 INTERLOCKED WITH 24 VAC & 115 VAC APPLIANCE CONTROL CIRCUITS

The circuit board of the MAC-3 is designed for a simple three wire interlock with up to three separate burners.  Upon a call for heat the “hot”
leg of the burner circuit is intercepted and routed to the MAC-3 terminal strip.  The MAC-3 is activated, the power venter, draft inducer,
IN-FORCER or damper starts.  The proving switch makes and the intercepted “hot” leg is returned to the burner circuit, allowing the burner to
fire.  Plug-in relays must be purchased separately depending on control system voltage of appliance.

Use Tjernlund part # 950-1040 relay For 24 VAC control systems
Use Tjernlund part # 950-0480 relay For 115 VAC control systems 

1

ELECTRICAL SPECIFICATIONS TABLE

Optional Limit (Spill Switch)

Used in conjunction with Optional Alarm
Sequencer

115 VAC Proven “HOT” From Fan Prover

115 VAC Neutral To Inducer / Venter / IN-FORCER

115 VAC “HOT” To Inducer / Venter 
/ IN-FORCER motor & Fan Prover

Auxiliary Operation Switch
(i.e. Manual or Gas Pressure) 

115 VAC Input From Disconnect Switch

Aux. Motor in parallel with H & N used for 
additional Power Venter, Inducer, IN-FORCER

Aux. Prover contacts in series with H & PH
contacts on output terminals

Appliance # 2
Interlock

Appliance # 1
Interlock

Appliance # 3
Interlock

MAC-3 CIRCUIT BOARD FEATURES

Aux. Limit switch in series with
optional limit on terminal strip

Optional Alarm Sequencer proves Fan
Prover Operation (not limit operation)

Содержание 950-0484

Страница 1: ...must be installed on optional limit location if it is not being utilized 2 Blue and Yellow wires from Fan Prover must be connected to Auxiliary Prover 3 4 contacts 3 Red wires from High Limit must be...

Страница 2: ...CONTENTS Cautions 1 Electrical Wiring Electrical Specifications Circuit Board Features 1 Output Power Venter Draft Inducer IN FORCER Damper Wiring Diagrams 2 3 Burner Input Wiring Diagrams 4 5 Alterna...

Страница 3: ...e hot leg of the burner circuit is intercepted and routed to the MAC 3 terminal strip The MAC 3 is activated the power venter draft inducer IN FORCER or damper starts The proving switch makes and the...

Страница 4: ...wiring on bottom of page 2 Our HSUL Series GPAK J 1 Series and Commercial HS 3 4 5 Series utilize our part 950 1040 relays which can be plugged into the MAC 3 for 24V control systems The HSUL Series G...

Страница 5: ...TJERNLUND MODEL SS1 OR SS2 SIDESHOT VENT SYSTEM MAC 3 WIRED WITH A POWER VENTER DRAFT INDUCER OR IN FORCER WITH A MOTOR GREATER THAN 9 AMPS TJERNLUND MODELS INCLUDE THE XL DRAFT INDUCER HS 5 POWER VE...

Страница 6: ...included with these instructions depict two burners interlocked with the MAC 3 To wire a third burner to the MAC 3 purchase the proper control voltage plug in relay and wire according to the diagram...

Страница 7: ...5 MAC 3 WIRED WITH UP TO THREE OIL BURNERS WITH R8184G CONTROLS BURNER MOTOR LESS THAN 7 AMPS MAC 3 WIRED WITH UP TO FIVE 24V GAS BURNERS AND ONE POWER VENTER DRAFT INDUCER OR IN FORCER...

Страница 8: ...6 MAC 3 WIRED WITH A POWER VENTER OR DRAFT INDUCER AND A COMMERCIAL IN FORCER MAC 3 CIRCUIT BOARD WIRING SCHEMATIC...

Страница 9: ...0480 4PDT Isolation Relay 950 0481 Alarm Sequencer 950 0478 Circuit Board only 950 0484 WHAT IS NOT COVERED Product installed contrary to our installation instructions Product that has been altered n...