TJERNLUND 950-0484 Скачать руководство пользователя страница 2

MODEL

MAC-3 

MULTIPLE APPLIANCE CONTROL 

Copyright © 1999, Tjernlund Products, Inc.  All rights reserved.

P/N 8504043

REV.  A 5/99

OWNER INSTRUCTIONS, DO NOT DESTROY

Recognize this symbol as an indication of important Safety Information!

THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED
SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND
OPERATION OF THIS UNIT.  READ THESE INSTRUCTIONS THOROUGHLY
BEFORE ATTEMPTING INSTALLATION OR OPERATION.  FAILURE TO FOLLOW
THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION,  ADJUST-
MENT, SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE, ELECTRI-
CAL SHOCK, CARBON MONOXIDE POISONING, EXPLOSION, OR PERSONAL
INJURY OR PROPERTY DAMAGE.

!

PLEASE READ CAREFULLY AND KEEP ON JOB 

SITE  FOR FUTURE REFERENCE.

For Interlocking one Power Venter, Draft Inducer 

IN-FORCER

TM

or Damper with up to three burners

TABLE OF CONTENTS

Cautions ..........................................................................................................................................................................1
Electrical Wiring

Electrical Specifications & Circuit Board Features .....................................................................................................1
Output Power Venter, Draft Inducer, IN-FORCER & Damper Wiring Diagrams ....................................................2, 3
Burner Input Wiring Diagrams  ...............................................................................................................................4, 5
Alternative Wiring Diagrams  ..................................................................................................................................5, 6

MAC-3 Wired With up to Five Gas Burners and One Power Venter, Draft Inducer or IN-FORCER................5
MAC-3 Wired With a Power Venter or Draft Inducer and a Commercial IN-FORCER ....................................6

MAC-3 Circuit Board Schematic  ....................................................................................................................................6
Replacement Parts & Warranty.......................................................................................................................................7

DESCRIPTION

The MAC-3 is used for wiring up to 3 heating appliances with a single Draft Inducer, Power Venter, IN-FORCER or 115V Damper.  It
is suitable for both 24 VAC and 115 VAC control systems for gas and oil burners.  Plug-in relays must be purchased separately
depending on control system voltage of appliance.

Use Tjernlund part # 950-1040 relay For 24 VAC control systems.
Use Tjernlund part # 950-0480 relay For 115 VAC control systems. 

TJERNLUND PRODUCTS, INC.

1601 Ninth Street • White Bear Lake, MN 55110-6794
PHONE (800) 255-4208 • (651) 426-2993 • FAX (651) 426-9547
Visit our web site • www.tjernlund.com

Содержание 950-0484

Страница 1: ...must be installed on optional limit location if it is not being utilized 2 Blue and Yellow wires from Fan Prover must be connected to Auxiliary Prover 3 4 contacts 3 Red wires from High Limit must be...

Страница 2: ...CONTENTS Cautions 1 Electrical Wiring Electrical Specifications Circuit Board Features 1 Output Power Venter Draft Inducer IN FORCER Damper Wiring Diagrams 2 3 Burner Input Wiring Diagrams 4 5 Alterna...

Страница 3: ...e hot leg of the burner circuit is intercepted and routed to the MAC 3 terminal strip The MAC 3 is activated the power venter draft inducer IN FORCER or damper starts The proving switch makes and the...

Страница 4: ...wiring on bottom of page 2 Our HSUL Series GPAK J 1 Series and Commercial HS 3 4 5 Series utilize our part 950 1040 relays which can be plugged into the MAC 3 for 24V control systems The HSUL Series G...

Страница 5: ...TJERNLUND MODEL SS1 OR SS2 SIDESHOT VENT SYSTEM MAC 3 WIRED WITH A POWER VENTER DRAFT INDUCER OR IN FORCER WITH A MOTOR GREATER THAN 9 AMPS TJERNLUND MODELS INCLUDE THE XL DRAFT INDUCER HS 5 POWER VE...

Страница 6: ...included with these instructions depict two burners interlocked with the MAC 3 To wire a third burner to the MAC 3 purchase the proper control voltage plug in relay and wire according to the diagram...

Страница 7: ...5 MAC 3 WIRED WITH UP TO THREE OIL BURNERS WITH R8184G CONTROLS BURNER MOTOR LESS THAN 7 AMPS MAC 3 WIRED WITH UP TO FIVE 24V GAS BURNERS AND ONE POWER VENTER DRAFT INDUCER OR IN FORCER...

Страница 8: ...6 MAC 3 WIRED WITH A POWER VENTER OR DRAFT INDUCER AND A COMMERCIAL IN FORCER MAC 3 CIRCUIT BOARD WIRING SCHEMATIC...

Страница 9: ...0480 4PDT Isolation Relay 950 0481 Alarm Sequencer 950 0478 Circuit Board only 950 0484 WHAT IS NOT COVERED Product installed contrary to our installation instructions Product that has been altered n...

Отзывы: