Operation

Initial Start-Up

1.

Connect the power cord to a standard 115-Volt, Single Phase, 60 Hertz, or 220-Volt, 50/60 Hertz, grounded power source.

Verify that the circuit is sized to provide sufficient amperage as noted on the 

THRC

 data plate.

2.

Locate the “ON/OFF” switch on the right side of the unit. The switch is a maintain contact rocker type.

3.

Turn the 

THRC

 unit on by pressing downward on the raised portion of the rocker switch. A light whirring

 

sound will be

heard as the motor starts. Within 5 to 10 seconds, the module will start to provide clean air into the environment.

Speed Adjustment

Note: 

THRC

 

HF 

unit

s

 

are

 set on high speed at the factory.

 TLRC LF units are set to OFF.

1.

To change speeds, remove the 

supply

 grille by pulling down and lifting out.

2.

Turn the 3-speed switch (or solid state speed control) to the desired setting on the 

THRC

 

HF

 or 

L

F

.

3.

Replace the 

supply

 grille when finished.

Filter Change Indicator

1.

Locate the airflow indicator on the right side of the unit above the “ON/OFF” switch. On high speed, the light will turn on

when there is insufficient pressure, indicating the need for a filter change.  It is recommended to change prefilter.  If the

filter change indicator light is still illuminated, it is recommended to replace the HEPA filter. The airflow indicator should

not be used as the only guide for when a filter change is necessary. The unit should be checked at each use to ensure

recommended room air changes per hour are being met.

2.

The filter change indicator light can be adjusted by adjusting the pressure switch which can be seen on the 

b

ack panel of

the 

THRC

.  For setting the light, block the lower intake grill approximately 75% while the unit is on high speed.  The

pressure switch should be set to have the light flicker while covered 75%.  Once the restriction is removed, the light should

go off.  If the intake grille is completely covered, the light should be solid on.

3.

The air velocity generated by the unit may be checked using an airflow measurement device. 

For the THRC HF t

he

volume of air entering

 

the  lower  intake  grille  should  be  approximately  560  CFM  (951  m

3

/h)  on  low,  690  CFM  (1172

m

3

/h)  on  medium,  and

 

800 CFM (1359 m

3

/h) on high with a new filter.  Air volume on the 

THRC

 

LF

 should be

approximately 70 CFM (118 m

3

/h) to 370 CFM (628 m

3

/h) depending on the position of the speed control with a new filter.

Recirculation Mode

1.

The  

THRC

 unit is set at the factory on the 100% air recirculation mode.

2.

The room air change rate of the unit will depend on both the  

THRC

 speed setting and the size of the room.

3.

For maximum recirculation efficiency

 in a patient room

, the unit should be placed between the entry door and the patient’s

bed or the activity

 

area (see Figure 1 below).  However, the unit will function effectively at other locations within the room.

Содержание THRC High Flow

Страница 1: ...Redefine your comfort zone www titus hvac com INSTALLATION OPERATION MANUAL Titus HEPA Room Cleaner High Flow Low Flow Configurations...

Страница 2: ...rt zone www titus hvac com IOM THRC HF LF Table of Contents Introduction 3 Installation 4 Operation 5 Maintenance Service 7 Troubleshooting 10 Wiring Diagram 11 Specifications 13 Replacement Parts 14...

Страница 3: ...e pressure isolation room Simply roll the THRC into a standard room connect flexible ducting to the 6 in 152 mm collar on the top of the unit for partial exhaust or to the optional 8 in 204 mm flanged...

Страница 4: ...unit in its final operating position 3 Lock the wheel locks on the casters to keep the unit from accidental repositioning Initial Start Up NOTE THECDCREQUIRESTHATQUANTITATIVELEAKAGEANDFILTERPERFORMAN...

Страница 5: ...he airflow indicator should not be used as the only guide for when a filter change is necessary The unit should be checked at each use to ensure recommended room air changes per hour are being met 2 T...

Страница 6: ...aust Collar with Flange is available to convert the THRC unit to the 100 exhaust mode 1 Remove the front exhaust grille by pulling down and lifting out 2 Place the optional 8 inch 203mm exhaust collar...

Страница 7: ...leaks Maintenance Service CAUTION PROPER PROTECTIVE EQUIPMENT AND MEASURES MUST BE USED AT ALL TIMES DURING UNIT CLEANING AND MAINTENANCE CHECK WITH YOUR SAFETY OFFICE TO ASSURE THE CLEANING SOLUTIONS...

Страница 8: ...cess panel The rear panel may now be lifted off Primary Filter Replacement The CDC recommends that in any application HEPA filters should be maintained meticulously and should be carefully installed b...

Страница 9: ...f the unit 4 Remove the old cord and replace with the new one by following the steps above in reverse order On Off Switch 1 With the back panel removed unplug the white connector on the switch and squ...

Страница 10: ...r can now be disposed of as general waste Phenolic Decontamination ln facilities where the above decontamination procedures are prohibited or not feasible the unit can be disinfected by the following...

Страница 11: ...amperage and distribution frequency 5 Check for down stream obstructions or erratic isolation room ventilation balance 6 Replace HEPA filter if the air velocity remains low after checking all other ca...

Страница 12: ...12 IOM THRC Redefine your comfort zone www titus hvac com IOM THRC HF LF Wiring Diagrams Cont THRC Low Flow Wiring Diagram...

Страница 13: ...r MERV8 multi pleat anti microbial pleated prefilter with frame Motor 1 3 HP 0 25 kW direct drive three speed continuous duty Exhaust Port 6 inch 152 4mm Duct Collar THRC Low Flow Dimensions 38 25 H x...

Страница 14: ...RC 1 11055 8 inch A C Collar with Flange for 100 1 267745 001 Intake Grille Painted 1 37453 Exhaust Grille 1 THRC High Flow UV Part No Description Quantity S62954 WIRED Motor 1 3 HP 3 Speed 115V 1 S63...

Страница 15: ...Plate for THRC 1 11055 8 inch A C Collar with Flange for 100 1 267745 001 Intake Grille Painted 1 37453 Exhaust Grille 1 THRC Low Flow UV Part No Description Quantity S267793 001 Motor 1 4 HP 3 Speed...

Страница 16: ...16 IOM THRC Redefine your comfort zone www titus hvac com IOM THRC HF LF Airflow Measurement Testing...

Страница 17: ...605 Shiloh Rd Plano TX 75074 ofc 972 212 4800 fax 972 212 4884 Redefine your comfort zone www titus hvac com...

Отзывы: