Supported End Points, Clusters & Attributes
The following clusters will need to be bound in order for the sensors to report valid data:
[0x0402] Measurement: Temperature
[0x040D] Concentration Cluster
[0x0405] Measurement: Relative Humidity
[0x0001] General: Power Configuration
For full details on sensor End Points, Clusters & Attributes
contact Titan Products for Technical Manual.
FCC Information
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions:
(1) this device may not cause harmful interference
(2) this device must accept any interference received, including interference that may cause undesired operation.
•
The sensor is to be wall mounted at approx. 1.5m from floor
level.
•
The sensor should be mounted in an area representative on
the environment to be measured and must be away from
direct sunlight, draughts, window / door openings and
heating / cooling sources.
•
Ensure the sensor is installed in the correct orientation*. See
Fig. 1.0.
•
The sensor should not be used outside of its operating
temperature range of 0 to 50°C.
•
The sensor should not be used outside of its operating
humidity range of 5-80% RH.(non-condensing)
•
The sensor is for indoor use only.
•
The sensor is IP20 rated and should be used in
environments where this is suitable. Where dust, water,
moisture, chemical gasses and contaminant ingress is
possible, an alternative product should be used.
•
The sensor should be mounted using the fixing holes
provided.
•
The stated battery life is estimated based on Titan Products’
recommended minimum, maximum, delta change
reporting and polling settings.
•
It is recommended that the battery is replaced during
regular maintenance work.
•
It is the responsibility of the buyer/installer to ensure
the sensor is suitable for integration in to their ambient
temperature monitoring system.
•
The sensor is designed for the monitoring and
transmission of ambient temperature, humidity and CO2
levels only.
•
It is recommended that the receiving Zigbee Wireless
controller should be set up to alarm if out of range
conditions are transmitted by the sensor.
•
Battery status clusters are available in the sensor device.
These clusters should be used in a maintenance program
to monitor when the battery needs replacing.
•
It is the installer’s responsibility to ensure a site survey is
completed ensuring the sensor location is suitable for the
environment to allow consistent and stable transmissions
between the sensor(s) and receiving device. Repeaters
may be required.
•
It is the customer’s/installer’s responsibility to ensure the
sensor standards are acceptable for the country or state
the device is being installed within.
•
Solvents in the air derived from sources such as paints,
cleaning products and adhesives can have a detrimental
impact on the sensor cell. All sensors should therefore
be installed after the space has been decorated and any
flooring fitted. The sensors should also be kept away
from adhesives and should the housing require cleaning
a dry non-solvent based product must be used. Do not
spray any liquid or cleaning products directly onto the
ventilated housing. Exposing the sensor to such solvents
or moisture will invalidate the product warranty.
Do not
blow directly on to the CO2 cell within the sensor, this
can damage the cell membrane and could cause incorrect
readings
Battery Information
Please make sure batteries are disposed of in accordance with EC Directive 2006/66/EC, amended by EU Directive 2008/12/EC or in
line with your territory battery disposal guidelines.
It is important not to short-circuit, crush, disassemble, heat above 100°C, incinerate, or expose the batteries to water. Do not solder
directly to the cell. The Recommended batteries for the Titan Products wireless sensors are 3.7V 2600mAH AA size Lithium-Thionyl
Chloride. These are not rechargeable. All batteries should be stored in a clean, cool, dry and ventilated area. When installing or
replacing a battery please make sure the polarity is correct. Batteries are not covered by the Titan Products product warranty.
To reset an end device; remove the battery, press and hold the PCB push button down while re-inserting the battery. Once the
battery is inserted, release the PCB push button.
Upon resetting, the device will restore the factory default settings for the minimum, maximum and delta change reporting along
with the polling intervals. Once reset the device will search for strongest Zigbee 3.0 network and attempt to join as described above.
Factory Reset