background image

t: +44 (0)161 406 6480 ● e: [email protected]  ● w: www.titanproducts.com

UK DESIGNED, DEVELOPED AND MANUFACTURED

Ref: SKU 224

Updating the controllers with new software or restoring from a backup:

From with the Update tap, select the controllers you would like to update or restore and press the Update Controllers 

button.

Browse and select the file from the connected PC or Laptop you would like to use to update the controllers. The update 

will then begin.

Once updated, 

Firmware Success 

will show. The controllers are now updated to the new software.

Содержание NETMASTER TP-NM-R/2000

Страница 1: ...NETMASTER TP NM R 2000 BACnet MS TP to IP Router c w Remote Access...

Страница 2: ...with the DIN rail mounted enclosure Backup and Restore functionality allows the TP NM R 2000 to update the firmware of any connected Titan MS TP devices within the network Features Full compatible wi...

Страница 3: ...titanproducts com w www titanproducts com UK DESIGNED DEVELOPED AND MANUFACTURED Ref SKU 224 Dimensions Connections 90mm 160mm 32mm BACnet RS485 MSTP 3 Wire COM ive ive LED Ethernet IP RJ45 IP Reset P...

Страница 4: ...rollers are on the MS TP network the number of controllers may be increased but this will depend on the network traffic the baud rate being used and the length route of the cable A termination resisto...

Страница 5: ...information is shown once logged in Note It is possible to reset the IP address and username password to their default settings by pressing down the IP reset button for approximately 10 seconds The LE...

Страница 6: ...t should all use the same subnet mask Default Gateway The default is 192 168 1 254 This should be set to the IP address of the router that is assumed to know how to forward packets on to other network...

Страница 7: ...main active in the absence of Termination Time messages being sent Use a value of 0 to indicate a permanent connection BBMD BACnet Broadcast Management Device FDR Foreign Device Registration Setup The...

Страница 8: ...gnostics The TP NM R 2000 includes a Diagnostics webpage which provides real time information of the routers performance and active applications This is designed to help with any troubleshooting while...

Страница 9: ...Titan controllers on the network via the Titan Products Remote Access App download The Titan Products App is available for download via the Apple App Store and the Google Play Store for Android devic...

Страница 10: ...toring from a backup From with the Update tap select the controllers you would like to update or restore and press the Update Controllers button Browse and select the file from the connected PC or Lap...

Страница 11: ...lity Building Blocks Supported Annex K DS RP A B Data Sharing ReadProperty A B DS RPM A B Data Sharing ReadPropertyMultiple A B DS WP A B Data Sharing WriteProperty A B DS WPM A B Data Sharing WritePr...

Страница 12: ...on Application_Software_Version Location max 100 characters Description max 100 characters Protocol_Version Protocol_Revision Protocol_Services_Supported Protocol_Object_Types_Supported Object_List Ma...

Страница 13: ...her Device Address Binding Is static device binding supported This is currently necessary for two way communication with MS TP slaves and certain other devices Yes No Networking Options Router Clause...

Страница 14: ...er must be setup for the Network 192 168 1 x There must be no other device on the network with the IP address 192 168 1 151 To setup your network router please consult the manual Once setup connect yo...

Страница 15: ...ESIGNED DEVELOPED AND MANUFACTURED Ref SKU 205 You should see the following page From here you will need to click the Local Area Connection After clicking you will be presented with a window where you...

Страница 16: ...ttings for the adapter Select Internet Protocol Version 4 TCP IPv4 and then click the Properties button The following properties window will be shown Select Use the following IP address and set the IP...