Table 2: Remote Control Remote Control Codes
Code # Code Type
Description
Code 1
Over Temperature
Temperature is greater than or equal to 95° F while
the Lights Output is enabled.
Code 2
High Temperature
Temperature is greater than or equal to 95° F for
an excess of 30 minutes while the Lights output is
disabled.
Code 3
Low Temperature
Temperature is less than or equal to 45° F for an
excess of 30 minutes.
Code 4
High Humidity
Humidity above 80% for an excess of 30 minutes.
Code 5
Low Humidity
Humidity below 30% for an excess of 30 minutes.
Code 6
High CO
2
CO
2
is greater than or equal to 5000 ppm.
Code 7
Empty CO
2
Tank
Injecting CO
2
for an excess of 30 minutes and CO
2
levels have not reached setpoint (daytime mode
only).
Code 8
No Measured Light
Light output has been enabled for a minimum of 15
minutes and no light is detected.
Code 9
No Measured Darkness
Light output has been disabled for a minimum of 15
minutes and light is detected.
Code 10
Power Interrupted
Unable to complete lighting schedule (power outage
likely).
Code 20
Temperature Sensor Error Sensor module is unable to get temperature reading
from temperature detector.
Code 21
RH Sensor Error
Sensor module is unable to get RH reading from
detector.
Code 22
RH Sensor Saturated
Sensor module has detected that RH detector is
saturated.
Code 23
CO
2
Sensor Error
Sensor module is unable to get CO
2
readings from
CO
2
detector.
Code 24
RTC Error
Remote Control is unable to get time from the real
time clock.
Remote Sensor LED:
The tri-colored LED on the remote sensor is used to display the status
of the Hyperion
®
2 by: color, flashes, and blinking frequency. In general,
a
green
LED indicates the controller is functioning normally. When the
LED is
yellow
, it indicates that there is a problem with the wireless
communication. A
red
LED is used to indicate an error with the controller
or one of its sensors. Refer to Table 3 for further details.